BBV28581  05/2010
Code
Name/Description
Adjustment range
Factory setting
I_O-
Input Output menu 
(continued)
tOL
Application Overload time delay
0 to 100 s
0 s
This function can be used to stop the motor in the event of an application overload. This is not a motor or 
drive thermal overload. If the motor current exceeds the 
 
LOC
, an 
tOL
 is activated. Once this time delay 
tOL
 has elapsed, if the current 
is still greater than the overload threshold 
LOC
 -10%, the drive will stop running and display 
 
Process overload.
Overload detection is only active when the system is in steady state (speed reference reached).
A value of 0 will disable application overload detection.
FtO
T
Time delay before automatic start for the 
overload fault
0 to 6 min
0 min
If Atr = YES the drive restarts automatically after an overload fault 
OLC
 once this time delay has elapsed.
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of 
Maximum restart time
 
tAr
 page 
 must 
exceed that of this parameter by at least one minute.
Visible only if 
Application Overload time delay
 
tOL
 above is not set to 
nO
.
LOC
T
Application Overload threshold
70 to 150% of nCr
90% of of nCr
Visible only if 
Application Overload time delay
 
tOL
 above is not set to 
0
.
This parameter is used to detect an "application overload". 
LOC
 can be adjusted between 70 and 150% 
of the nominal drive current. This is not a motor or drive thermal overload.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-
LOC
Motor current
LOC
 -10%
Drive stop
on 
OLC
 detected fault
tOL
tOL
(hysteresis)
t