BBV28581  05/2010
59
Code
Name/Description
Adjustment range
Factory setting
drC-
Motor control menu 
(continued)
PFL
T
Flux Profile
0 to 100%
20%
It defines the magnetizing current at zero frequency, as a % of the rated magnetizing current
Adjustment of PUMP law.
Frequency
Visible only if 
page 
 is set to 
PUMP
SFr
T
Switching frequency
2 to 16 kHz
4 kHz
Switching frequency setting.
In the event of overheating, the drive automatically decreases the switching frequency. 
It is restored to its original value when the temperature returns to normal.
CAUTION
RISK OF DAMAGE TO THE DRIVE
On ATV12
pppp
M2 ratings, if the filters are disconnected, the drive’s switching frequency must not exceed 4 kHz. 
Failure to follow these instructions can result in equipment damage.
SFt
Switching frequency type
HF1
HF1
HF2
The motor switching frequency will always be modified (reduced) when the internal temperature of the 
drive is too high.
v
HF1: Heating optimization. 
Allows the system to adapt the switching frequency according to the motor frequency.
v
HF2: Motor noise optimization (for high switching fequency). 
Allows system to keep a constant chosen switching frequency (SFr) whatever the motor frequency (rFr).
In the event of overheating, the drive automatically decreases the switching frequency. 
It is restored to its original value when the temperature returns to normal.
nrd
Motor noise reduction
nO
nO
YES
Noise means audible noise. Depending on the environment it must be possible to adjust the motor noise. 
Random frequency modulation avoids possible resonance noises that can occur at fixed frequency.
v
No 
v
Yes 
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-