Sterling GG-30 사용자 설명서

다운로드
페이지 44
8
GAS PIPING
 To avoid damage or possible personal injury, do not connect gas piping to this unit 
until a supply line pressure/leak test has been completed. Connecting the unit before completing the 
pressure/leak test may damage the unit gas valve and result in a fi re hazard.
 Do not rely on a shut-off valve to isolate the unit while conducting gas pressure/leak 
tests. These valves may not be completely shut off, exposing the gas valve to excessive pressure and 
damage.
NOTICE: If more than one unit heater is to be served 
by the same piping arrangement, the total cu. ft./hr. 
input and length of pipe must be considered.
NOTICE: If the gas unit heater is to be fi red with LP 
gas, consult your local LP gas dealer for pipe size 
information.
NOTICE: HEATER INSTALLATION FOR USE WITH 
PROPANE  (BOTTLED) GAS MUST BE MADE BY A 
QUALIFIED L.P. GAS DEALER OR INSTALLER. HE 
WILL ENSURE THAT PROPER JOINT COMPOUNDS 
ARE USED FOR MAKING PIPE CONNECTIONS; 
THAT AIR IS PURGED FROM LINES; THAT A 
THOROUGH TEST IS MADE FOR LEAKS BEFORE 
OPERATING THE  HEATER;  AND THAT  IT  IS 
PROPERLY  CONNECTED TO THE  PROPANE  GAS 
SUPPLY SYSTEM.
Before any connection is made to the existing line 
supplying other gas appliances, contact the local 
gas company to make sure that the existing line is of 
adequate size to handle the combined load.
1.  Determine the required Cu. Ft./Hr. by dividing the input  by 1000.  For SI/Metric measurements: Convert BTU/Hr. to kilowatts.  Multiply the 
units inputs (kW) by 0.0965 to determine Cu. Meters./Hr. 2. FOR NATURAL GAS: Select pipe size directly from the table. 3. FOR PROPANE 
GAS: Multiply the Cu. Ft./Hr. value by 0.633; then, use the table.  4. Refer to the metric conversion factors listed in the General Safety section for 
SI Unit measurement conversions.
Table 2 - Gas Pipe Size
PIPE SIZING
To provide adequate gas pressure to the gas unit heater, 
size the gas piping as follows:
1.  Find the cu. ft./hr. by using the following formula:
 
 
 
       Input 
 
 
 
Cu. ft./hr. =
   BTU   
2.  Refer to Table 2. Match “Length of Pipe in Feet” with 
appropriate “Gas Input - Cu. Ft./Hr.” fi gure. This fi gure 
can then be matched to the pipe size at the top of 
the column.
 Example:
 
It is determined that a 67 foot (20.4m) run of gas pipe 
is required to connect a 75 MBTU gas unit heater to 
a 1,000 BTU/cu ft. (0.29kW) natural gas supply.
   
75,000 
BTU/Hr
 
     1,000 BTU/cu. ft.    
= 75 Cu. ft./hr
 
Using Table 2, a 3/4 inch pipe is needed.
NOTE: See General Safety Information section for 
English/Metric unit conversion factors.
 
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less, 
 
and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)
 
 
(Based on a 0.60 Specifi c Gravity Gas)
 Nominal  
 
 
Iron 
Internal 
Length of Pipe,  Feet (meters)  
 
  
Pipe Size
 
Dia.
 10 20 30 40 50 60 70 80 90 100 
125 
150 
175 
200
  in. 
in. 
(3.0)  (6.1)  (9.1)  (12.2) (15.2) (18.3) (21.3) (24.4) (27.4) (30.5) (38.1) (45.7) (53.3) (61.0)
 
 
1/2 
0.622 
175 
120 97 82 73 66 61 57 53 50 44 40 37 35
   
 
(4.96) (3.40) (2.75) (2.32) (2.07) (1.87) (1.73) (1.61) (1.50) (1.42) (1.25) (1.13) (1.05) (0.99)
 
 
3/4 0.824 360 250 200 170 151 138 125 118 110 103  93  84  77  72
   
 
(10.2) (7.08) (5.66) (4.81) (4.28) (3.91) (3.54) (3.34) (3.11) (2.92) (2.63) (2.38) (2.18) (2.04)
 
1  1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135
   
 
(19.3) (13.2) (10.6) (9.06) (8.07) (7.36) (6.80) (6.23) (5.80) (5.52) (4.96) (4.53) (4.11) (3.82)
 
1/4 
1.380 
1400 950 770 660 580 530 490 460 430 400 360 325 300 280
   
 
(39.6) (26.9) (21.8) (18.7) (16.4) (15.0) (13.9) (13.0) (12.2) (11.3) (10.2) (9.20) (8.50) (7.93)
 
1/2 
1.610 
2100 
1460 
1180 990 900 810 750 690 650 620 550 500 460 430
   
 
(59.5) (41.3) (33.4) (28.0) (25.5) (22.9) (21.2) (19.5) (18.4) (17.6) (15.6) (14.2) (13.0) (12.2)
 2  2.067 3950 2750 2200 1900 1680 1520 1400 1300 1220 1150 1020  950  850  800
   
 
(112)  (77.9) (62.3) (53.8) (47.6) (43.0) (39.6) (36.8) (34.5) (32.6) (28.9) (26.9) (24.1) (22.7)
 
1/2 2.469 6300 4350 3520 3000 2650 2400 2250 2050 1950 1850 1650 1500 1370 1280
   
 
(178)  (123)  (99.7) (85.0) (75.0) (68.0) (63.7) (58.0) (55.2) (52.4) (46.7) (42.5) (38.8) (36.2)
 3  3.068 11000 7700 6250 5300 4750 4300 3900 3700 3450 3250 2950 2650 2450 2280
   
 
(311) (218) (177) (150) (135) (122) (110) (105) (97.7) (92.0) (83.5) (75.0) (69.4) (64.6)
 4  4.026 23000 
15800 
12800 
10900 9700 8800 8100 7500 7200 6700 6000 5500 5000 4600
   
 
(651) (447) (362) (309) (275) (249) (229) (212) (204) (190) (170) (156) (142) (130)