Honeywell herculine 2000 사용자 설명서

다운로드
페이지 128
Specifications 
Technical and Operating Specifications 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
7/08  
 
 
 
HercuLine
®
 2002 
HercuLine
®
 2001 
HercuLine
®
 2000/2003 
Feedback 
Slidewire emulation - Provides 
output voltage ratiometric to 
shaft position and 
potentiometric to supply voltage 
(1 Vdc to 18 Vdc) without a 
slidewire. Emulates a 100 ohm 
to 1000 ohm slidewire. 10 mA 
output maximum. 
 
 
Communications 
Modbus RTU or optional HART
™ 
NA 
Operating Temperature 
–40°C to +75 °C (–40°F to +170 °F) 
-40°C to +85 °C (-40°F to 
+185 °F) 
Position sensing 
Non-contact position sensor 
1000 ohm film potentiometer 
Dual 1000 ohm film 
potentiometers  
(not on 2003) 
Sensitivity 
0.2 % to 5 % of 90° span, proportional to deadband 
NA 
Hysteresis 
Less than 0.4 % of full scale 
 
NA 
Deadband 
0.2 % to 5 % of 90° span, programmable.  Shipped at 0.5 % 
NA 
Repeatability 
0.2 % of 90° span 
NA 
Repositions  
(minimum @ 90 or 150 
degree stroke) 
Table 1 option –050- 
Table 1 option –100- 
Table 1 option –200- 
Table 1 option –400- 
Table 1 option –600- 
 
 
 
160 
 
290 
 
450 
 
700 
 
900  
 
 
 
120  
250  
400  
400  
400  
 
 
 
500  
Voltage/ Supply 
Stability 
0.25 % of span with +10/–15 % voltage change 
NA 
Temperature 
Coefficient 
Less than 
± 0.030 % of span per degree C for 0 °C to 50 °C 
Less than 
± 0.05 % of span per degree C for –40 °C to 75 °C 
NA 
Zero Suppression 
90 % of span. 
NA 
Input Filters 
Selectable spike and low pass filters. 
NA 
Solid State Motor 
Control 
Two triac switches for clockwise or anti-clockwise motor operation. 
Transient voltage protection provided. 
NA 
Failsafe operation 
If input signal exceeds configured input range.  Selectable and 
adjustable. 
NA 
Direction of Rotation 
Field programmable 
Wire swap  
Duty Cycle 
Continuous