Honeywell herculine 2000 사용자 설명서

다운로드
페이지 128
Set Up and Calibration Procedures 
Set Up Procedure 
36 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Set Up Procedure 
Each of the set up groups and their functions are either pre-configured at the factory or set to their default 
values.  Tables 8 through 19 list and describe the options available in each set up group.  The following 
procedure shows you the key press sequence to access any set up group or any associated Function 
parameter. Make sure lock set up group “LOCK” function is set to “NONE” or “CAL.”  Also some 
parameters require that you enter a security password before you access or change the parameter.   
You can use this procedure to access the set up groups and select all parameters.   
 
Table 9 Set Up Procedure Using Display and Keypad 
Step 
Operation 
Press 
Result 
Enter Set Up Mode 
SET UP 
 
Upper Display
 =   
 SET 
Lets you know you are in the set up mode and a set up group 
title is being displayed in the lower display. 
 
Lower Display
  =  
INPUT 
This is the first set up group you see when you press SET UP. 
Select any Set Up 
Group 
SET UP 
Successive presses of the SET UP key will display the other set 
up group titles as listed in Table 8Error! Reference source not 
found.
You can also use the
or 
 keys to scroll through the set up 
groups in both directions. 
Stop at the set up group title that describes the group of 
parameters you want to configure. Then proceed to the next 
step. 
Select a Function 
Parameter 
FUNCTION 
Upper Display
4-20
Shows the current value or selection for the 
function prompt in the selected set up group. 
IN TYP
Lower Display
Shows the first function prompt within the selected 
set up group. 
Example display shows Input group function prompt “IN TYP” 
and the selection. 
Select other 
function parameters 
FUNCTION 
Successive presses of the FUNCTION key will sequentially 
display the other function prompts of the selected set up group. 
Stop at the function prompt that you want to change, and then 
proceed to the next step.