Set Up and Calibration Procedures 
Calibration 
70 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Calibrate Motor 
Use the procedure in Table 26 to calibrate the actuator motor for 0% and 100% input signal 
 
 
ATTENTION 
For a motor calibration to be saved, you must complete the procedure.  The calibration will not 
be saved if you exit without completing the steps of the procedure.   
 
 
 
ATTENTION 
When calibrating the motor to a short stroke range, you must reset the end-of-travel limit 
switches.  See Setting End-of-Travel Limit Switches.   
Table 26 Motor Calibration Procedure 
 
Step 
Operation 
Press 
Result 
Enter Calibration 
Mode 
SETUP 
until you see 
Upper Display
 =   
CAL
 
Lower Display
  =  
MOTOR 
 
 
 FUNCTION 
Upper Display
 =   
DIS
 
Lower Display
  =  
CALMTR
 
 
 
 or 
 key 
Upper Display
 =   
BEGN
 
Lower Display
  =  
CALMTR
 
Calibrate Zero (0%) 
FUNCTION 
Upper Display
 =   
APLY
 
Lower Display
  =  
MTR LO 
• 
Use the Handwheeel or AUTO/MANUAL switch to manually 
drive the actuator motor to its low position.  
• 
Wait 5 seconds, then go to step 3. 
Calibrate Span 
(100%) 
FUNCTION 
Upper Display
 =   
APLY
 
Lower Display
  =  
MTR HI 
• 
Use the Handwheeel or AUTO/MANUAL switch to manually 
drive the actuator motor to its high position.  
• 
Wait 5 seconds, then go to step 4. 
 FUNCTION 
Calibration for zero and span motor positions are now saved.  
Motor calibration is complete.   
NOTE:  The display will automatically go to the CAL CURENT 
set up display.  See Table 27.  You may also exit calibation 
mode by pressing the DISPLAY or SETUP keys.