Honeywell TB7100A1000 사용자 설명서

다운로드
페이지 24
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
21
63-2675—03
— Users cannot make changes to the temperature setpoint or 
any schedule, system, or fan settings.
— The only features available are HOLIDAY and OVERRIDE. 
— To unlock the screen, see Advanced Settings section. 
Temperature Recovery
The thermostat is equipped with a feature to eliminate 
guesswork when setting a schedule. That is, the user need not 
know the amount of time for the HVAC system to bring the 
space to temperature (without overshoot) prior to the 
scheduled time.The thermostat manages that automatically.
Simply set the program schedule to the desired time to have 
the space at comfort temperature. In addition, program the 
temperature to this comfort temperature. The thermostat 
activates the heating or cooling at the proper time to reach the 
scheduled temperature at the scheduled time.
NOTE: The setpoint changes gradually to use economical 
stages and avoid overshoot.
For example—the space will be occupied at 8:00 AM and the 
desired temperature is 70°F. Set the OCC 1 period for 8:00 AM 
and 70°F. The thermostat turns on the heat prior to 8:00 AM to 
raise the temperature to 70°F by 8:00 AM.
The thermostat provides an alert that the heating or cooling 
system is coming on before a scheduled time by displaying 
“Recovery” on the screen.
Minimum-Off Timer Compressor Protection
The thermostat has an adjustable Minimum-Off Timer that can 
be set from zero to five minutes (Factory Setting—five 
minutes). The Minimum-Off Timer can be bypassed through 
the Installer System Test or it can be bypassed permanently by 
setting the Minimum-Off Timer to 0 minutes in the Installer 
Setup. The Minimum-Off Timer is activated after the 
compressor turns off:
— If the thermostat is system powered (common wire), the 
Minimum-Off Timer is also activated upon initial startup and 
after power interruptions.
— If there is a call for cooling or heating during the Minimum-
Off Time, the thermostat displays “Wait.”
— When the Minimum Off Timer expires, “Cool On” or “Heat 
On” (heat pumps only)” appears solidly in the display and 
the compressor and fan turn on.
Temperature Sensor Operation and Checkout
Allow outdoor or indoor temperature sensor to absorb the air 
for a minimum of five minutes before taking a reading. See the 
Sensor instructions for more information.
NOTE: The C7189U, TR21 and TR21-A Temperature 
Sensors are calibrated at the factory and cannot 
be recalibrated in the field.
C7189U Remote Indoor Temperature Sensor
Operation
When installed with Thermostat ISU 0340 set to 3, the remote 
inside temperature is displayed on the Thermostat Home 
Screen as Inside Temperature. The thermostat internal 
temperature sensor is not used.
The C7189U can be used to provide one remote sensor input 
or as a temperature averaging network with multiple TR21 
Sensors connected, as shown in Fig. 28.
Checkout
For best results, allow C7189U Wall Mount Temperature 
Sensor to absorb the air moving through the room for a 
minimum of twenty minutes before taking a resistance 
measurement.
With an accurate thermometer (±1°F [0.5°C]) measure the 
temperature at the sensor location, allowing time for the 
thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of 
C7189U wiring terminals. Use an ohmmeter to measure the 
resistance across the sensor. Then compare sensor accuracy 
with the temperature/resistance curve in Fig. 40.
Fig. 40. 10K ohm sensor resistance versus temperature.
TR21 Remote Temperature Sensor
Operation
When installed with Thermostat ISU 0340 set to 3 or 4, the 
remote inside temperature is displayed on the Thermostat 
Home Screen as Inside Temperature. The thermostat internal 
temperature sensor is not used.
The TR21 can be used to provide one remote sensor input or 
as a temperature averaging network with multiple TR21 
Sensors connected, as shown in Fig. 25 through 27.
Checkout
For best results, allow TR21 Wall Mount Temperature Sensor 
to absorb the air moving through the room for a minimum of 
twenty minutes before taking a resistance measurement.
With an accurate thermometer (±1°F [0.5°C]) measure the 
temperature at the sensor location, allowing time for the 
thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of the 
wiring terminals. Use an ohmmeter to measure the resistance 
across the sensor. Then verify the sensor accuracy with the 
temperature/resistance in Fig. 41.
TEMPERATURE (DEGREES)
o
F
-40
-20
0
20
40
60
80
100 120
-20
-30
-40
-10
40
RESIST
ANCE (OHMS)
10K OHM AT 
77
o
F (25
o
C)
220K
190K
160K
130K
100K
90K
60K
30K
o
C
M22823
0
10
20
30
50
0K