TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
63-2675—03
6
Table 5. Terminal Designation Descriptions.
NOTES:
1.
When used in a single-transformer system, leave 
metal jumper wire in place between Rc and R. If 
used on a two-transformer system, remove metal 
jumper wire between Rc and R.
2.
Common wire is optional when thermostat is used 
with batteries. When using separate transformers 
for heating and cooling, the common must come 
from the cooling transformer.
3.
If thermostat is configured for a heat pump in the 
Installer Setup, configure changeover valve for 
cool (O-factory setting) or heat (B).
4.
Sensor wires must have a cable separate from the 
thermostat control cable.
Conventional System Wiring
Fig. 11. Typical wiring of single transformer 1H/1C system.
Fig. 12. Typical hookup of dual transformer 1H/1C system.
Terminal 
Designation
Description
Rc 
(see Note 1)
Power for cooling—connect to secondary side 
of cooling system transformer.
(see Note 1)
Power for heating—connect to secondary side 
of heating system transformer.
Y
Compressor output.
(see Note 2)
Common wire from secondary side of cooling 
system transformer.
W1
Heat relay. Auxiliary heat relay for heat pump, 
PTAC.
G
Fan relay. Low fan speed for fan coil and PTAC.
G2
Fan relay. Medium fan speed for fan coil only.
G3
Fan relay. High fan speed for fan coil and 
PTAC.
O/B 
(see Note 3)
Changeover valve for heat pumps.
S1 
(See Note 4)
Indoor remote sensor, remote setback, or 
changeover input.
S2 
(See Note 4)
Indoor remote sensor, remote setback, or 
changeover input.
COMPRESSOR CONTACTOR
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
FAN RELAY
POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION 
IS OPTIONAL.
1
2
3
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
L1  
(HOT) 
L2 
24 VAC 
M27416
HEAT RELAY
COMPRESSOR CONTACTOR
M27417
HEAT RELAY
FAN RELAY
COOLING
TRANSFORMER
HEATING
TRANSFORMER
POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 
REMOVE FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION 
IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT 
TO THE COOLING TRANSFORMER SECONDARY.
1
3
2
3
L1 
(HOT)
L2
1
24 VAC
L1  
(HOT) 
L2 
24 VAC
C
G
Y
O/B
RC
R
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
W1
G2
G3
S1
S2