7.2 Communication options 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
129
 
7.2 
Communication options 
The S7-1200 offers several types of communication between CPUs and programming 
devices, HMIs, and other CPUs.  
 
 
WARNING 
If an attacker can physically access your networks, the attacker can possibly read and write 
data. 
The TIA Portal, the CPU, and HMIs (except HMIs using GET/PUT) use secure 
communication that protects against replay and "man-in-the-middle" attacks. Once 
communication is enabled, the exchange of signed messages takes place in clear text 
which allows an attacker to read data, but protects against unauthorized writing of data. 
The TIA Portal, not the communication process, encrypts the data of know-how protected 
blocks. 
All other forms of communication (I/O exchange through PROFIBUS, PROFINET, AS-i, or 
other I/O bus, GET/PUT, T-Block, and communication modules (CM)) have no security 
features. You must protect these forms of communication by limiting physical access. If an 
attacker can physically access your networks utilizing these forms of communication, the 
attacker can possibly read and write data. 
For security information and recommendations, please see our "Operational Guidelines for 
Industrial Security" on the Siemens Service and Support site. 
 
PROFINET 
PROFINET is used for exchanging data through the user program with other 
communications partners through Ethernet: 
●  PROFINET supports 16 IO devices with a maximum of 256 submodules. PROFIBUS 
allows 3 independent PROFIBUS DP Masters, supporting 32 slaves per DP master, with 
a maximum of 512 modules per DP master. 
●  S7 communication 
●  User Datagram Protocol (UDP) protocol 
●  ISO on TCP (RFC 1006) 
●  Transport Control Protocol (TCP) 
PROFINET RT IO controller 
As an IO controller using PROFINET RT, the CPU communicates with up to 16 PN devices 
on the local PN network or through a PN/PN coupler (link). Refer to PROFIBUS and 
PROFINET International, PI (
) for more information.