7.6 PROFIBUS 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
147
 
Assigning the PROFIBUS address 
In a PROFIBUS network, each device is assigned a PROFIBUS address. This address can 
range from 0 through 127, with the following exceptions:  
●  Address 0: Reserved for network configuration and/or programming tools attached to the 
bus 
●  Address 1: Reserved by Siemens for the first master 
●  Address 126: Reserved for devices from the factory that do not have a switch setting and 
must be re-addressed through the network 
●  Address 127: Reserved for broadcast messages to all devices on the network and may 
not be assigned to operational devices 
Thus, the addresses that may be used for PROFIBUS operational devices are 2 through 
125. 
In the Properties window, select the "PROFIBUS address" configuration entry. STEP 7 
displays the PROFIBUS address configuration dialog, which is used to assign the 
PROFIBUS address of the device.  
 
Table 7- 10  Parameters for the PROFIBUS address 
Parameter 
Description 
Subnet 
Name of the Subnet to which the device is connected. Click the "Add new subnet" button to create a 
new subnet. "Not connected" is the default. Two connection types are possible: 
 
The "Not connected" default provides a local connection. 
 
A subnet is required when your network has two or more devices. 
Parameters 
Address 
Assigned PROFIBUS address for the device 
Highest address 
The highest PROFIBUS address is based on the active stations on the 
PROFIBUS (for example, DP master). Passive DP slaves independently 
have PROFIBUS addresses from 1 to 125 even if the highest PROFIBUS 
address is set to 15, for example. The highest PROFIBUS address is 
relevant for token forwarding (forwarding of the send rights), and the token 
is only forwarded to active stations. Specifying the highest PROFIBUS 
address optimizes the bus.