PID is easy 
 
8.3 PID_Compact instruction ErrorBit parameters 
 
Easy Book 
178
 
Manual, 03/2014, A5E02486774-AF 
ErrorBit (DW#16#...) 
Description 
20000 
Invalid value at the SubstituteValue tag: Value has an invalid number 
format. 
PID_Compact uses the output value low limit as the output value. 
Note: If automatic mode was active before the error occurred, 
ActivateRecoverMode = TRUE, and the error is no longer pending, 
PID_Compact switches back to automatic mode. 
40000 
Invalid value at the Disturbance parameter: Value has an invalid number 
format. 
Note: If automatic mode was active and ActivateRecoverMode = FALSE 
before the error occurred, Disturbance is set to zero. PID_Compact remains 
in automatic mode. 
Note: If pre-tuning or fine tuning mode was active and ActivateRecoverMode 
= TRUE before the error occurred, PID_Compact switches to the operating 
mode that is saved in the Mode parameter. If Disturbance in the current 
phase has no effect on the output value, tuning is not canceled. 
 
1
  Note: If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE, 
PID_Compact remains in automatic mode. 
2
  Note: If pre-tuning or fine tuning mode was active before the error occurred and 
ActivateRecoverMode = TRUE, PID_Compact switches to the operating mode that is saved in the 
Mode parameter. 
3
  Note: If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE, 
PID_Compact outputs the configured substitute output value. As soon as the error is no longer 
pending, PID_Compact switches back to automatic mode. 
4
  Note: If ActivateRecoverMode = TRUE before the error occurred, PID_Compact cancels the tuning 
and switches to the operating mode that is saved in the Mode parameter.