8.7 Commissioning the PID controller 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
191
 
PID start value control 
You can edit the actual values of the PID configuration parameters so that the behavior of 
the PID controller can be optimized in online mode. 
Open the "Technology objects" for your PID controller and its "Configuration" object. To 
access the start value control, click the "eyeglasses icon" in the upper left corner of the 
dialog: 
 
You can now change the value of any of your PID controller configuration parameters as 
shown in the figure below. 
You can compare the actual value to the project (offline) start value and the PLC (online) 
start value of each parameter. This is necessary to compare online/offline differences of the 
Technology object data block (TO-DB) and to be informed about the values that will be used 
as current values on the next Stop-to-Start transition of the PLC. In addition, a compare icon 
gives a visual indication to help easily identify online/offline differences: 
 
The figure above shows the PID parameter screen with compare icons showing which 
values are different between online and offline projects. A green icon indicates that the 
values are the same; a blue/orange icon indicates that the values are different.