Web server for easy Internet connectivity 
 
9.2 Constraints that can affect the use of the Web server 
 
Easy Book 
196
 
Manual, 03/2014, A5E02486774-AF 
9.2 
Constraints that can affect the use of the Web server 
The following IT considerations can affect your use of the Web server:  
●  Typically, you must use the IP address of the CPU to access the standard Web pages or 
user-defined Web pages, or the IP address of a wireless router with a port number. If 
your Web browser does not allow connecting directly to an IP address, see your IT 
administrator. If your local policies support DNS, you can connect to the IP address 
through a DNS entry to that address. 
●  Firewalls, proxy settings, and other site-specific restrictions can also restrict access to the 
CPU. See your IT administrator to resolve these issues. 
●  The standard Web pages use JavaScript and cookies. If your Web browser settings 
disable JavaScript or cookies, enable them. If you cannot enable them, some features 
are restricted. Use of JavaScript and cookies in user-defined Web pages is optional. If 
used, you must enable them in your browser. 
●  The Web server supports Secure Sockets Layer (SSL). You can access the standard 
Web pages and user-defined Web pages with an URL of either http://ww.xx.yy.zz or 
https://ww.xx.yy.zz, where "ww.xx.yy.zz" represents the IP address of the CPU. 
●  Siemens provides a security certificate for secure access to the Web server. From the 
Introduction standard Web page, you can download and import the certificate into the 
Internet options of your Web browser. If you choose to not import the certificate, you will 
get a security verification prompt every time you access the Web server with https://. 
Number of connections 
The Web server supports a maximum of 30 active HTTP connections. Various actions 
consume the 30 connections, depending on the Web browser that you use and the number 
of different objects per page (.css files, images, additional .html files). Some connections 
persist while the Web server is displaying a page; other connections do not persist after the 
initial connection.  
If, for example, you are using Mozilla Firefox 8, which supports a maximum of six persistent 
connections, you could use five browser or browser tab instances before the Web server 
starts dropping connections. In the case where a page is not using all six connections, you 
could have additional browser or browser tab instances.  
Also be aware that the number of active connections can affect page performance.  
 
 
Note 
Log off prior to closing Web server 
If you have logged in to the Web server, be sure to log off prior to closing your Web browser. 
The Web server supports a maximum of seven concurrent logins.