Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 사용자 설명서

제품 코드
6AV6651-7KA01-3AA4
다운로드
페이지 364
 
Easy to use the online tools 
 
11.6 Using the force table 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
263
 
If the CPU is executing the user program from a write-protected memory card, you cannot 
initiate or change the forcing of I/O from a watch table because you cannot override the 
values in the write-protected user program. Any attempt to force the write-protected values 
generates an error. If you use a memory card to transfer a user program, any forced 
elements on that memory card will be transferred to the CPU.  
 
 
Note 
Digital I/O points assigned to HSC, PWM, and PTO cannot be forced 
The digital I/O points used by the high-speed counter (HSC), pulse-width modulation (PWM), 
and pulse-train output (PTO) devices are assigned during device configuration. When digital 
I/O point addresses are assigned to these devices, the values of the assigned I/O point 
addresses cannot be modified by the force function of the force table.  
 
 
Startup 
RUN 
A  The clearing of the I memory area is not 
affected by the Force function. 
  While writing Q memory to the physical 
outputs, the CPU applies the force value as 
the outputs are updated. 
B  The initialization of the outputs values is 
not affected by the Force function. 
  When reading the physical inputs, the CPU 
applies the force values just prior to copying 
the inputs into I memory. 
C  During the execution of the startup OBs, 
the CPU applies the force value when 
the user program accesses the physical 
input. 
  During the execution of the user program 
(program cycle OBs), the CPU applies the 
force value when the user program accesses 
the physical input or writes the physical 
output. 
D  The storing of interrupt events into the 
queue is not affected. 
  Handling of communication requests and self-
test diagnostics are not affected by the Force 
function. 
E  The enabling of the writing to the 
outputs is not affected. 
  The processing of interrupts during any part of 
the scan cycle is not affected.