 Modu-Fire
® 
Gas-Fired Boiler 
Installation 
 
 8 
WARNING! 
This boiler should not be installed with an automatic 
damper on the flue.  Damper failure could create an 
explosion hazard. 
 
In Canada, the boiler is certified for installation with a 
“Power Venter” by the Canadian Gas Association 
when installed with the “listed accessories.”  Consult 
your local distributor for information on proper selec-
tion.   
The venting system and the horizontal portions of the 
venting system shall be supported to prevent sagging. 
Consult your local vent supplier for correct vent sizing 
and structural support requirements.  Vent diameter is 
dictated by the length and height of horizontal and ver-
tical portions of the vent installation and the materials 
of construction.  It is not necessarily the same size as 
the boiler connection.  Correct sizing should be based 
on High fire input at a nominal -.04" w.c. draft pres-
sure at the boiler outlet with a gross stack temp of 325º 
F and CO
2
 ratings at 7.5%. 
 
3.6.1  Vent Elbows 
 
 
 
 
 
The first turn from horizontal to vertical should be 
made with a 135° boot tee.  A tee cover with a conden-
sate drain shall be provided at the bottom of the boot 
tee.  The condensate drain must be routed to a sewer 
drain trap or pump in accordance with local codes.  
Refer to diagram under Vent Elbows. 
 
3.6.2  Barometric Damper 
This boiler is certified for operation without a baro-
metric damper.  P-K does not recommend the use of 
one.  
 
3.6.3  Automatic Vent Damper  
 
WARNING! 
This equipment, as manufactured, MUST NOT be 
used with an automatic vent damper. 
 
 
3.6.4  Flue Connection 
The connection from the boiler to the vent should be 
as direct as possible and the upward slope of any hori-
zontal breaching should be at least 1/4 inch per linear 
foot.  This boiler should not be connected into any por-
tion of a mechanical draft system operating under 
positive pressure.  Provisions must be made for sup-
ports to prevent contact of the vent with combustible 
surfaces. 
Note:  Make sure that the weight of the vent is not 
supported 
by the boiler vent collar.  The collar is not 
designed to support the weight of the vent.  Structural 
support and spacing from combustible surfaces must 
be in accordance with the vent manufacturer's re-
quirements. 
 
3.6.5  Vent Termination 
The minimum vent height above the flue outlet must 
be five (5) feet and the vent should extend at least 
three (3) feet above the roof / snowline, or at least two 
(2) feet above the highest part of any structure within 
ten (10) feet of the vent.  
 
6' min. 
Pitch toward 
boiler 1/4" per 
foot minimum. 
Boot Tee /135º 
Tee 
Trap Loop 
3" min. 
To sewer trap or 
condensate drain. 
Condensate Line