  MACH®  Series
 
Gas-Fired Boiler 
Maintenance 
 
 
Page  34 
5.5.1  Manual Reset Service Codes 
 
Code Lockout 
Description 
E 00 
False flame. 
A flame signal is present when it shouldn’t be. 
E 02 
Flame failure. 
The burner did not light on startup, or loss of flame during run. 
E 03 
Gas Valve error. 
Check all gas valves electrical connections. 
E 04 
General lockout. 
The power was lost after a lockout.  The control loses the description of the lockout on 
power loss. 
E 05 
Internal control failure. 
Call for service. 
E 06 
Internal control failure. 
Call for service. 
E 07 
Internal control failure. 
Call for service. 
E 08 
Air pressure switch open. 
The air pressure switch failed to close to indicate sufficient air flow to start the boiler. 
E 11 
Internal control failure. 
Call for service. 
E 12 
External limit open. 
One of the external limits has opened. (High/Low Gas Pressure, High Temp, Low water). 
E 13 
Internal control failure. 
Call for service. 
E 14 
Internal control failure. 
Call for service. 
E 15 
Internal control failure. 
Call for service. 
E 16 
Internal control failure. 
Call for service. 
E 17 
Internal control failure. 
Call for service. 
E 18 
Outlet high limit temp. 
The outlet water temperature has exceeded the internal high limit temperature setting. 
E 19 
Return high limit temp. 
The return water temperature has exceeded the internal high limit temperature setting. 
E 25 
Outlet temp rapid change. 
The outlet water temperature is increasing too fast.  Indicating low flow condition. 
E 28 
No blower feedback. 
The blower should be running but it is not, or the feedback signal has been interrupted. 
E 29 
Blower feedback will not zero.  The blower will not go to zero speed even though it should be off. 
E 31 
Outlet sensor shorted. 
The outlet temperature sensor is short circuited. 
E 32 
Return sensor shorted. 
The return temperature sensor is short circuited. 
E 33 
DHW sensor shorted. 
The DHW temperature sensor is short circuited. 
E 35 
Flue sensor shorted. 
The flue gas temperature sensor is short circuited. 
E 36 
Outlet sensor open. 
The outlet temperature sensor is indicating an open circuit.  
E 37 
Return sensor open. 
The return temperature sensor is indicating an open circuit. 
E 38 
DHW sensor open. 
The DHW sensor is indicating an open circuit. 
E 40 
Flue sensor open. 
The flue gas temperature sensor is indicating an open circuit. 
E 44 
Internal control failure. 
Call for service. 
E 52 
High flue temp. 
The flue temperature has exceeded the maximum allowable setting. 
E 60 
Internal control failure. 
Call for service. 
 
 
Note:  When an Internal Control Failure occurs, as identified by E-Codes listed above, the failure is internal to the 
MCBA and replacement of the MCBA is required.  A qualified service technician must be called to replace the 
MCBA device.