Proline Promass 80 PROFIBUS PA
Commissioning
55
Assignment of the measured variables to the AI module
The AI module can transmit different measured variables to the PROFIBUS master (Class 1).
The measured variables are assigned to the Analog Input function blocks 1 to 4 by means of the local 
display or with the aid of an operating program (e.g. FieldCare) in the CHANNEL function:
COMMUNICATION 
→ BLOCK SELECTION: select an Analog Input function block → 
CHANNEL: select a measured variable
Possible settings
Factory setting:
Example:
You want to cyclically transmit the mass flow to the PROFIBUS master (Class 1) by means of the 
Analog Input function block 1 (module AI, slot 1) and the temperature by means of the Analog Input 
function block 2 (module AI, slot 2).
1.
COMMUNICATION 
→ BLOCK SELECTION: select ANALOG INPUT 1, then select 
CHANNEL = MASS FLOW
2.
COMMUNICATION 
→ BLOCK SELECTION: select ANALOG INPUT 2, then select 
CHANNEL = TEMPERATURE
Measured variable
ID for CHANNEL function
MASS FLOW
277
VOLUME FLOW
273
CORRECTED VOLUME FLOW
398
DENSITY
281
REFERENCE DENSITY
402
TEMPERATURE
285
Module
Analog Input 
function block
Measured variable
Unit 
ID for CHANNEL 
function
AI (slot 1)
1
MASS FLOW
kg/s
277
AI (slot 2)
2
VOLUME FLOW
m/h
273
AI (slot 3)
4
DENSITY
kg/l
281
AI (slot 4)
6
TEMPERATURE
K
285