Eclipse Combustion VeriFlame Single Burner Monitoring System 사용자 설명서

다운로드
페이지 42
38
Eclipse Veri-Flame Instruction Manual 818 -2/02
Lockout
For purge & modulation models: Combustion air flow limit
switch opened for more than two seconds once initially proven.
Status
For purge & modulation models: Combustion air flow limit switch
opened; if “recycle” has been selected, the Veri-Flame will restart the
sequence after air failure (see “Recycle Mode” on page 14).
Lockout
For purge & modulation models: Combustion air flow limit
switch did not make within ten seconds of fan being energized.
Status
For purge & modulation models: Combustion air flow limit
switch closed within ten seconds of fan being energized.
Status
For modulation models only: Modulating motor is sent to au-
tomatic operation.
Status
Main flame of burner is proven in the automatic modulation mode;
flame strength is XX.XV (volts DC). Elapsed time is shown in
hours:minutes:seconds.
Lockout
For modulation models only: Internal control failure; replace
controller.
Status
For purge & modulation models: Blower motor is energized
at the start of pre-purge.
Lockout
Main flame lost during operation in the automatic modulation mode.
Burner number (X) given of failed unit.
Lockout
For modulation models only: High damper or high purge rate
switch did not make at the end of pre-purge to high fire.
Lockout
Internal control failure; replace controller.
Lockout
Internal control failure; replace controller.
Status
The controller has completed its internal checks and is standing by
for the interlocks to close.
Lockout
For modulation models only: Low fire switch is open just prior
to pilot trial for ignition.
Lockout
Main flame was not established during the main burner trial for
ignition.
Status
Main flame lost during automatic modulation; control will recycle
once if “recycle” has been selected.
M
ESSAGE
T
YPE
E
XPLANATION
Table 9.2
  Remote Display Diagnostic Messages (Listed Alphabetically)
AIR FAILURE
XX:XX:XX LOCKOUT
AIR FAILURE
RECYCLING
AIR NOT PROVEN
XX:XX:XX LOCKOUT
AIR PROVEN
AUTOMATIC
MODULATION
D-INTERNAL FAIL
XX:XX:XX:XX LOCKOUT
FAN ENERGIZED
FLAME FAILURE
XX:XX:XX LOCKOUT
BURNER ON XX.XV
TIME=XXXX:XX:XX
HI DAMPER/POVC
XX:XX:XX LOCKOUT
K-INTERNAL FAIL
XX:XX:XX LOCKOUT
L-INTERNAL FAIL
XX:XX:XX LOCKOUT
LIMITS OPEN
TIME=XXXX:XX:XX
LOW FIRE FAIL
XX:XX:XX LOCKOUT
MAIN FLAME FAIL
XX:XX:XX LOCKOUT
MAIN FLAME FAIL
RECYCLING