Specifications
I
NTRODUCTION
Specifications
This section gives a detailed overview of Veri-Flame specifications and dimensions.
2
(continued onto next page)
P
ARAMETER
D
ESCRIPTION
Supply
• Series 5602 & 5605: 120 VAC (+10%, -15%), 50/60 Hz standard.
  Series 5603: 240 VAC (+10%, -15%), 50/60 Hz standard.
  Internal power consumption: 12 VA (excluding external connected loads).
Temperature Ranges
Unit
Model Nos.
Temperature Range
Veri-Flame
All Models
-40˚ to +60˚C (-40˚ to +140˚F)
90˚ U.V.  Scanner
5600-90A
-20˚ to +60˚C
(0˚ to 140˚F)
U.V.  Scanner
5600-91
-20˚ to +125˚C
(0˚ to +257˚F)
NEMA4 UV Scanner
5600-91N4
-20˚ to +125˚C
(0˚ to +257˚F)
I.R.  Scanner
5600-92B
-40˚  to +110˚C (-40˚  to +230˚F)
UV/IR Scanner
5600-92SC
-20˚ to +80˚C
(0˚ to +176˚F)
Self-Check U.V.
5602-91
-20˚ to +60˚C
(0˚ to +140˚F)
Remote Display
5602DB
0˚ to 50˚C
(32˚ to 122˚F)
Remote Display
5602DBP
0˚ to 50˚C
(32˚ to 122˚F)
Flame Failure Response
  3 seconds ±0.5 seconds.
Trial For Ignition (TFI)
 
 No Purge & Purge Models:
Series 5602 & 5603: five or 10 seconds selectable.
Series 5605: ten or 15 seconds selectable.
  Modulating Model: 5 or 10 seconds selectable
Pilot Interrupt (if selected)
 10 seconds.
Purge Time
  Selectable from 0-225 seconds in 15 second increments.
Output Ratings for 120 VAC
Function
Terminals
Inductive Load
(maximum total connected
Gas Valve
3, 5
175VA, 1/10 HP
10 amps
 load not to exceed 15 amps)
Ignition
4
375 VA
10 amps
Motor or Contactor
8
470 VA, 1/2 HP
16 amps
Output Ratings for 240 VAC
Function
Terminals
(maximum total connected
Valves, Ignition
3, 4, 5,
5 amps
 load not to exceed 15 amps)
Motors or Contactor
8
5 amps
Alarm
10, 11, 12, 13
5 amps
UL, CSA
Control Signal
A, 10, 11, 12, 13
175VA
10 amps
Relay Contact Rating
Resistive Load
Control
16 amps 
A
Relay Contact Rating
Resistive Load