INStALLAtION
Continued
Figure 10 - Checking Gas Joints for 
Propane/LP Gas
Control Valve 
Location
Propane/LP 
Supply Tank
Equipment Shutoff Valve
Figure 9 - Checking Gas Joints for 
Natural Gas
Gas Meter
Equipment Shutoff Valve
Control Valve Location
OPERAtING HEAtER
FOR YOUR SAFETY 
READ BEFORE LIGHTING
 WARNING: Keep flue open 
when operating unit.
 WARNING: If you do not fol-
low  these  instructions  exactly, 
a  fire  or  explosion  may  result 
causing property damage, per-
sonal injury or loss of life.
A.  This appliance has a pilot which must be 
lighted by hand. When lighting the pilot, 
follow these instructions exactly.
B.  BEFORE LIGHTING smell all around the 
appliance area for gas. Be sure to smell next 
to the floor because some gas is heavier than 
air and will settle on the floor.
  WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not 
use any phone in your building.
• Immediately call your gas supplier from 
a  neighbor’s  phone.  Follow  the  gas 
supplier’s instructions.
• If you cannot reach your gas supplier, call 
the fire department.
C.  Use only your hand to push in or turn the 
gas control knob. Never use tools. If the 
knob will not push in or turn by hand, don’t 
try to repair it, call a qualified service tech-
nician or gas supplier. Force or attempted 
repair may result in a fire or explosion.
D.  Do not use this appliance if any part has 
been  under  water.  Immediately  call  a 
qualified service technician to inspect the 
appliance and to replace any part of the 
control system and any gas control which 
has been under water.
3.  Check all joints from gas meter to equipment 
shutoff valve for natural gas or propane/LP sup-
ply to equipment shutoff valve for propane/LP 
(see Figure 9 or 10). Apply noncorrosive leak 
detection fluid to all joints. Bubbles forming 
show a leak. 
4.  Correct all leaks at once.
PRESSURE TESTING HEATER GAS 
CONNECTIONS
1.  Open equipment shutoff valve (see Figure 8, 
page 9).
2.  Open main gas valve located on or near gas 
meter for natural gas or open propane/LP 
supply tank valve.
3.  Make sure control knob of heater is in the OFF 
position.
4.  Check all joints from equipment shutoff valve 
to control valve (see Figure 9 or 10). Apply 
noncorrosive leak detection fluid to all joints. 
Bubbles forming show a leak.
5.  Correct all leaks at once.
6.  Light heater (see Operating Heater). Check 
all other internal joints for leaks.
7.  Turn off heater (see To Turn Off Gas to Appli-
ance, page 10).