Honeywell MRP-2001E Manual Do Utilizador
Installation
ANN-BUS Devices
36
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
The following table shows the ANN-80 connections to the FACP.
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
"ANN-BUS" on page 71 in this manual for detailed programming information. Select the LCD
option for programming.
must be added to the system via FACP programming. Refer to the programming section titled
"ANN-BUS" on page 71 in this manual for detailed programming information. Select the LCD
option for programming.
FACP (TB3)
ANN-80 (TB1)
Terminal 4 GND (-)
Terminal 1 (-)
Terminal 3 PWR (+)
Terminal 2 (+)
Terminal 2 A (ANN-BUS)
Terminal 3 (A)
Terminal 1 B (ANN-BUS)
Terminal 4 (B)
Figure 2.17 ANN-80 Wiring to FACP
FACP
ANN-80
ANN-BUS and power wiring are
supervised and power-limited
supervised and power-limited
4 3 2 1
TB3
ann80 torp2001.cdr