SECTION 6: HEATER INSTALLATION 
6.1 General 
Heaters are designed for installation above 6' 
(1.8 m). These heaters must be installed within the 
heated space. Duct delivery systems are not 
permitted with axial fan units. When handling or 
supporting the heater from below, ensure that the 
weight is taken at the support points.
The gas or electrical supply lines must not be used 
to support the heater.
Do not locate the gas or electrical supply lines 
directly over the path of the flue products from the 
heater.
The heater must be installed in a location that is 
readily accessible for servicing.
The heater must be installed in accordance with 
clearances to combustibles as indicated on the wall 
tag and in this manual.
6.2 Suspension
Four suspension points (3/8" nuts) are located on 
the top of the heater. Drop rods must be 3/8" 
diameter mild steel minimum. 
When handling or supporting the heater from below, 
ensure that the weight is taken at the support points. 
For typical suspension, 
See Page 10, Figure 5.
Figure 5: Suspension Methods
WARNING
Crush Hazard
Use 3/8" threaded rod 
minimum.
Failure to follow these 
instructions can result in 
death, injury or property 
damage.