CDVSC7 & CDV7 Series Gas Fireplace
48
69D3011
BuRneR, pIloT anD ConTRol CoMpaRT-
MenT
Keep  the  control  compartment,  logs,  and  burner  areas 
surrounding the logs clean by vacuuming or brushing at 
least twice a year.  Make sure the burner porting, pilot air 
opening and burner air opening are free of obstructions 
at all times.
pIloT FlaMe
The flames from the pilot should be visually checked as 
soon  as  the  heater  is  installed  and  periodically  during 
normal operation. The pilot flame must always be pres-
ent when the fireplace is in operation. 
Figure 64. The 
pilot  flame  has  three  distinct  flames,  one  engulfing  the 
thermopile, one engulfing the thermocouple or sensor, and 
the other reaching to the main burner.
            
BuRneR
Inspect area around the injector. Remove any lint or foreign 
material with a brush or vacuum.
BuRneR FlaMe
The  flames  from  the  burner  should  be  visually  checked 
as soon as the heater is installed and periodically during 
normal operation. In normal operation, at full 
rate,  and  after  operating  for  about  15  to  30 
minutes, the flame should be yellow and slightly 
taller than the rear log. Figure 65
If the flame is blue and only in the center, turn 
off unit and let cool. After unit is cool, remove 
logs  and  check  to  make  sure  rock  wool  is 
placed correctly. Replace logs. 
noTe:  The  type  of  installation,  vent  system 
configuration, and wind effects may cause the 
flame patterns to vary.
CleanInG anD MaInTenanCe 
w
a
R
n
In
G
Turn off gas before servicing fireplace. It 
is  recommended  that  a  qualified  service 
technician perform these check-ups at the 
beginning of each heating season.
FP1943
pilot flame
Thermopile 
Thermocouple 
FP1943
LG638
CDV7 log flame
Figure 65 - 
Burner Flame Appearance 
LG638
Figure 64 - 
Pilot Flame 
FP2453
hooded pilot flames
Sensor
Thermopile
FP453
Signature 
Command 
System pilot
Millivolt Control 
pilot