GENERAL INSTALLATION INFORMATION
CODES
Adhere to all local codes or, in their absence, the latest edition of THE NATIONAL FUEL GAS CODE ANSI Z223.1 
or NFPA54 which can be obtained from…
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
or
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
ADEQUATE COMBUSTION AND VENTILATION AIR
This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided 
for adequate combustion and ventilation air.
The National Fuel Gas Code, (ANSI Z223.1/NFPA 54), defines a confined space as a space whose volume is less than 50 
cubic feet per 1,000 BTU per hour (4.8 m
3
 per kw) of the aggregate input rating of all appliances installed in that space. An 
unconfined space is defined as a space whose volume is not less than 50 cubic feet per 1,000 BTU per hour (4.8 m
3
 per kw) 
of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which 
the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.
UNUSUALLY TIGHT CONSTRUCTION IS DEFINED AS CONSTRUCTION WHERE…
a)   walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of 1 perm  
(6 x 10
11
 kg per pa-sec-m
2
) or less with openings gasketed or sealed;
b)  weather striping has been added on openable windows and doors, and
c)   caulking  or  sealants  are  applied  to  areas  such  as  joints  around  window  and  door  frames,  between  sole  plates 
and  floors,  between  wall-ceiling  joints,  between  wall  panels,  at  penetrations  for  plumbing,  electrical,  and  gas 
lines, and at other openings.