WDV Series Gas Fireplace
Vent InstallatIOn 
InstallatIOn plannInG 
There are two basic types of direct-vent installation:
•  
Horizontal Termination
•  
Vertical Termination
It is important to select the proper length of vent pipe for 
the type of termination you choose. It is also important to note the wall thickness. 
FOr hOrIZOntal terMInatIOn
Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every 
12" of run towards the termination below 7Z\x feet of vertical rise. With 7Z\x feet or more vertical 
rise off top of fireplace, the horizontal run may run level. NEVER run vent piping down. 
You may use up to three 90° elbows in this vent configuration. Refer to Vertical/Horizontal Ter-
mination Configurations on Page 14.
FOr VertIcal terMInatIOn
Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical 
rise in an attic or second story, and allow for sufficient vent height above the roof line. 
nOte: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios 
when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or 
a combination of  90° and 45° elbows up to a maximum of 270°. 
For two-story applications, firestops are required at each floor level. If an offset is needed in the 
attic, additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house.
Refer to Installing A Vent System in an Outside Chase below. If pipe is enclosed in chase, it is 
not exposed. 
It is very important that the venting system maintain its balance between the combustion air 
intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be 
strictly followed.
InstallInG a Vent systeM In an OutsIDe chase
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a 
building. A chase is required for such venting. 
W
arn
In
G
never run the vent pipe level or downward. 
this  may  cause  excessive  temperatures 
which could cause a fire. 
n
O
t
Ice
When installing in a chase, you should insulate the chase as you would the 
outside walls of your home. this is especially important in cold climates. 
Insulation should be considered a combustible material. Maintain proper 
clearances to all combustible materials. 
n
O
t
Ice
treatment  of  firestops  and  construction  of  the  chase  may  vary  from 
building  type  to  building  type.  these  instructions  are  not  substitutes 
for the requirements of local building codes. you must follow all local 
building codes.