VPAk eLeCTRONIC CONTROL FeATURes
Thermostat Compatibility: 
The VPAK Electronic Control is compatible with 
Friedrich 
RT4 and RT5 Thermostats. 
The VPAK Electronic control is also compatible 
with most standard Single Stage Heat/Cool 
Thermostats.  
NOTE:  Field supplied Thermostats MUST 
energize the fan circuit on a call for Heating 
or Cooling, and (when used with a Heat 
Pump Unit) MUST energize the “B” terminal 
in Heating in order for the unit to function 
correctly.
 
Compressor Time Delay: 
The Electronic control is equipped with a 
random (180 to 240 seconds) Compressor 
time delay that is initiated every time the 
compressor cycles “Off.”  The “delay on break” 
timer is initiated by the following actions: 
(1) Satisfying the temperature set point 
(2) Changing mode to fan only 
(3) Turning the unit off 
(4)  Restoring power after a failure
 
Note: The Compressor Time Delay feature is 
disabled during “Test Mode” operation. 
 
Fan delay
The Electronic Control is equipped with a 
feature that will start the fan 5 seconds 
EARLY 
(i.e. before compressor or heater) when unit 
cycles 
“ON.”  When the unit cycles “OFF” the 
fan will 
DELAY for 30 seconds in Cooling and 
15 seconds in Heating. 
Note: the fan delay is disabled during 
Test 
Mode operation.
Emergency Heat: 
The Electronic Control is equipped with a 
feature that allows servicer/end user to switch 
to electric heat operation when the compressor 
fails during the heating season, (See DIP 
switch position 7) until the compressor can be 
replaced.