installation
Connecting the Flue
 Flue  System
The provision for satisfactory fl ue termination must be made as 
described in BS 5440-1.
The appliance must be installed so that the fl ue terminal is expo-
sed to outdoor air.
The terminal must not discharge into another room or space such 
as an outhouse or lean-to.
It is important that the position of the terminal allows a free pas-
sage of air across it at all times.
The terminal should be located with due regard for the damage 
or discolouration that might occur on buildings in the vicinity, it 
must also be located in a place not likely to cause nuisance.
In cold or humid weather water vapour may condense on leaving 
the fl ue terminal.
The eff ect of such “steaming” must be considered.
If the terminal is less than 2 metres above a balcony, above ground 
or above a fl at roof to which people have access, then a suitable 
stainless steel terminal guard must be fi tted. 
The minimum acceptable spacing from the terminal to obstruc-
tions and ventilation openings are specifi ed in Fig. 1.
 - A Directly below an opening, window, etc 
300 mm
- B Horizontally to an opening, window, etc 
300 mm
- C Below gutters, soils pipes or drain pipes 
75 mm
- D Below eaves 
200 mm
- E From vertical drain pipe or soil pipe 
75 mm
- F From internal or external corner 
300 mm
- G Above ground, roof or balcony level 
300 mm
- H From a surface facing the terminal 
600 mm
- I   From a terminal facing a terminal 
1200 mm
- J  Vertically from a terminal on the same wall 
1500 mm
- K Horizontally from an terminal on the same wall 
300 mm
- L Fixed by vertical fl ue terminal
Fig. 1
11
mm
150 mm
Minimum Length = 500 mm
180 mm
Fig. 2