installation
To calculate the size of the heating installation, refer to the 
"Available pressure" graph below. 
Graph representing the available circulation pump pressure 
ΔT20
o
C
   
Before the equipment is used, for the fi rst time the trap 
must be fi lled with water. To do this, add approximately 
1/4 litre of water via the fl ue outlet before fi tting the fl ue 
system, or unscrew the cap on the trap positioned under-
neath the boiler, fi ll it with water and refi t it
Warning! Insuffi
  cient water in the trap can temporarily 
cause the fl ue gas to be expelled into the surrounding 
ambient air
Underfl oor heating
For appliances with underfl oor heating, it is possible but not 
necessary to fi t a safety thermostat onto the underfl oor heating 
outlet. For the electrical connection of the thermostat see the 
section on “Electrical connections - page 25”.
If the outlet temperature is too high, the boiler will stop both 
domestic hot water and the heating production and the error 
code 1 16 “fl oor thermostat contact open” will appear on the 
display. The boiler will restart when the thermostat is closed 
during automatic resetting.
If the thermostat cannot be installed, the underfl oor  heating 
equipment must be protected by a thermostatic valve, or by a by-
pass to prevent the fl oor from reaching too high a temperature.