Ariston 41-116-37 Manual Do Utilizador

Página de 72
22
installation
Fitting the Twin Pipe (Ø80 / 80)
 Note: See table for maximum and minimum fl ue runs.
Where it is not possible to terminate the fl ue within the distance 
permitted for coaxial fl ues, the twin fl ue pipe can be used by fi tting 
a special adaptor to the fl ue connector and using the aperture for 
the air intake located on top of the combustion chamber.
Always ensure that the fl ue is adequately supported, using one 
fl ue bracket per extension and avoiding low points. (ARISTON 
supply suitable clamps as Part No. 705778).
To utilise the air intake it is necessary to:
1) Take the air intake cover off  the top of the appliance
2) Assemble the fl ange on the header supplied with the boiler
3) Insert the header on the tube or the elbow up until the lower 
stop (you do not have to use the washer).
4) Insert the elbow/header in the boiler air intake hole and fasten 
it with screws.
The twin fl ue pipes can be fi tted with or without additional elbows 
and need no clamps, simply ensure that the lip seal is inserted in 
the female end of the fl ue pipe and push the extension piece fully 
into the previous section of fl ue pipe or elbow, check that the lip 
seal is not dislodged when assembling the fl ue (greasing the seal 
will aid assembly).
Twin pipe can also be converted back to Coaxial fl ue to enable 
vertical termination with a coaxial kit by using the pipe bridge 
(Twin - Coaxial Adaptor - Part No. 3318089).  When running the 
twin fl ue pipe vertically.
It is not possible to terminate concentrically horizontally. 
 
Termination is only possible with separate air and exhaust 
terminals.
 
When siting the twin fl ue pipe, the air intake and exhaust terminals 
must terminate on the same wall, the centres of the terminals 
must be a minimum of 280 mm apart and the air intake must 
not be sited above the exhaust terminal (refer to Fig. 10).  The air 
intake pipe can be run horizontally, however, the terminal and the 
fi nal 1 metre of fl ue must be installed either horizontally or with a 
slight fall away from the boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run be 
constructed of insulated pipe to prevent condense forming on 
the outside of the tube.
Ensure the exhaust tube has a minimum fall back to the boiler of 
1˚ / metre   (1˚ = 17.5mm/metre)
The maximum permissible fl ue length for twin fl ue is dependent 
on the type of run used (see table on page 24).
For further information relating to fl ue runs not illustrated, please 
contact the Technical Department on 0870 241 8180.