Ariston A/23 MFFI Manual Do Utilizador

Página de 28
14
B023
Remove the grommet “D” shown in photo 5, make a hole in it and pass
the room thermostat wire through.
Remove the link located on the terminal and connect the wire.
Replace the grommet and the terminal to their original positions, close the
cover on the grommet compartment and fasten the wire-clamp “C” in place.
If a remote time clock is to be fitted, disconnect the integral time clock plug 
from the P.C.B.
Using a volt-free switching time clock, connect the switching wires from the 
time clock following points 1-7 above.
10 If using a time clock and room thermostat, these must be connected in 
series as per points 1-9 above.
Note:
Only a two-wire type room thermostat can be used.
2.10 Room Thermostat 
Connection
3
4
5
6
7
D
C
B
C
1
A
2
In order to perform this procedure, remove boiler cover as indicated in section
3.2. Then proceed as follows:
Remove the screws “A” located on the bottom part of the boiler;
Widen the sides so that the control panel can be rotated.
Open the cover “B” on the left hand side of the compartment.
Insert the wire for the connection of the room thermostat into the wire
holder “C”, as indicated in photo 3.