AHE Series 4 Direct Vent Wall-Mounted Boilers — User’s Information Manual
Common problems and solutions
Symptom
Common Causes
Possible Corrections
Rapid cycling — 
boiler turns on and 
off frequently
Thermostat installed where drafts 
or heat affect reading
Locate thermostat on inner wall away from heat sources or cool 
drafts.
Heat anticipator in thermostat 
adjusted incorrectly
Adjust thermostat per manufacturer's instructions.
Incorrect limit setting
Set limit according to system needs. Maximum setting is 220˚F. 
Increase limit setting to decrease cycling.
Insufficient water flow through 
boiler
Check all valves to and from boiler. Return to proper setting.
Confirm circulator size.
Frequent release of 
water through relief 
valve
Expansion tank sized too small
Call qualified service technician to check expansion tank 
operation and size.
Flooded expansion tank
Call qualified service technician to check expansion tank 
operation.
Inoperative limit control
Call qualified service technician to replace limit control.
Need to frequently 
add makeup water
Leaks in boiler or piping
Have qualified service technician repair leaks at once to avoid 
constant use of makeup water. Makeup water can cause 
mineral deposits which, in turn, can cause boiler section failure. 
Do not use petroleum-based stop-leak compounds.
Black water 
condition
Oxygen corrosion due to leaks in 
boiler and piping
Have qualified service technician repair at once. Keep pH of 
water between 7.0 to 8.5.
Popping or 
percolating noise 
heard in boiler
Mineral deposits in sections due 
to constant use of makeup water
Call qualified service technician to de-lime boiler, if necessary. 
In some cases, deposits will be too heavy to remove with de-
liming procedures.
Have qualified service technician repair leaks to eliminate need 
for constant makeup water.
Incorrect pH of boiler water
Call qualified service technician to check pH level and correct. 
pH should be maintained between 7.0 to 8.5.
Insufficient water flow through 
boiler
Check all valves to and from boiler. Return to proper setting.
Confirm circulator size.
Metal flakes found in 
vent outlet or vent — 
flueway corrosion
Contaminated combustion air 
supply — See page 4 in this 
manual.
Remove any contaminating products. See page 3 in this 
manual.
Provide outside air for combustion. Kit available through Weil-
McLain distributor. Have qualified service technician pipe-up kit.
Condensation of combustion 
gases in boiler sections
Have qualified service technician inspect system piping and 
controls to verify proper regulation of return water temperature.
Some radiators or 
baseboard units do 
not heat or are noisy
Air in system
Bleed air from system through air vents in radiators or 
baseboard units.
Low system pressure
Fill to correct pressure.
Check for leaks in boiler or piping. Have qualified service 
technician repair at once.
High limit set too low
Adjust high limit to higher setting.