AHE Series 4 Direct Vent Wall-Mounted Boilers — User’s Information Manual
Boiler service and maintenance
The User’s Information Manual provides information to the boiler owner/user for routine operation and
maintenance and emergency shutdown. Detailed information on boiler installation, operation, start-up, service
and parts is included in the Boiler Manual. 
The Boiler Manual is intended only for use by a qualified installer/
service technician.
Maintenance schedule
Maintain the boiler using the maintenance schedule below. Have the boiler started up and serviced at least annually
by a qualified service technician to ensure boiler/system reliability.
Boiler maintenance
Service technician
(covered in Boiler Manual — for use only by a 
qualified service technician)
Owner maintenance
(see following pages for instructions)
A
N
NNUAL
 
ST
AR
T
-
UP
Inspect:
•  Reported problems
•  Boiler area
•  Air openings
•  Flue gas vent system (and air piping)
•  Main burner flames
•  Water piping
•  Boiler heating surfaces
•  Burners and base
Service:
•  Cleaning boiler heating surfaces
•  Blower motor
•  Oiled-bearing circulators
Start-up:
•  Perform start-up per manual
Check/test:
•  Gas piping
•  Cold fill and operating pressures
•  Air vents and air elimination
•  Blower motor assembly
•  Circulator with mixing valve
•  Limit controls and cutoffs
•  Expansion tank
•  Boiler relief valve
Review:
•  Review with owner
Daily
•  Check boiler area
•  Check air openings
•  Check boiler pressure/
temperature gauge
Monthly
•  Check boiler piping
•  Check venting system
•  Check boiler relief valve
•  Check automatic air vents
•  Main burner flames
Periodically
•  Test low water cutoff
•  Clean vent termination and air 
intake screens
Every 6 months
•  Operate relief valve
End of season
•  Shut down procedure