T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
63-4355—4
16
Setting Keypad Lockout Switch (T7300 only)
The DIP switch 1, on the thermostat back, activates the 
lockout features. The switch must be set ON (up) to activate 
the lockout feature (see Fig. 17).
NOTE:
The factory setting is off (down).
If keypad lockout is desired:
1.
Remove the thermostat from the subbase.
2.
Set the switch to ON.
3.
Enter the Installer Setup.
4.
Select option 25 to choose the level of keypad lockout 
(see Table 7).
5.
Activate the lockout by setting option 40 to 1.
Fig. 17. Set keypad lockout DIP switch 1.
PROGRAMMING
The thermostat operates at the Unoccupied temperature 
setting unless the thermostat is programmed. Table 10 shows 
the default temperature settings. (The program has four):
— Occupied heat.
— Occupied cool.
— Unoccupied heat.
— Unoccupied cool.
Table 10. Occupied and Unoccupied 
Default Temperature Settings.
The keyboard is located behind the thermostat cover. Up to 
sixteen keys are used to set, review and modify programmed 
times and temperature settings. The thermostat display shows 
day, time, program period and temperature.
The thermostat can be set for two Occupied and two 
Unoccupied times for each day of the week (28 independent 
time settings). Temporary Occupied key provides quick 
temporary temperature changes for increased occupant 
comfort. The Continuous Unoccupied key provides energy 
efficient operation for extended periods of time.
IMPORTANT
To program the thermostat, 24 Vac is required (turn 
on system power). The keyboard lockout feature 
must be disabled by setting the DIP switch 1 on the 
back of the thermostat to the Off position.
NOTE:
Before starting the program procedure, use Table 11 
to organize the program schedule.
Table 11. Occupied and Unoccupied Periods Start Times.
Setting Current Day/Time
1.
Press Set Current Day/Time
NOTE:
On initial power up or after an extended power 
loss, the display flashes 1:00 pm until a key 
is pressed.
2.
Press Day until the current day is displayed.
NOTE:
Sun = Sunday, Mon = Monday, Tue = Tuesday, 
Wed = Wednesday, Thu = Thursday, 
Fri = Friday, Sat = Saturday.
3.
Press increase
 ▲ 
or decrease 
 until the current time 
is displayed.
NOTE:
Tapping Set Current Day/Time changes the 
time in one hour increments.
4.
Press Run Program.
Control
Occupied
Unoccupied
Heating
70°F (21°C)
55°F (13°C)
Cooling
78°F (26°C)
90°F (32°C)
ON
1
2
M10235
BACK OF THERMOSTAT
1
2
1
2
DIP 1 IS ON
DIP 2 IS NOT USED.
Day
Occupied 
Period 1
Unoccupied 
Period 1
Occupied 
Period 2
Unoccupied 
Period 2
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
M4951B
Set Current
Day/Time
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
Mon
PM
Set Day/Time
M4952B
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
Day
PM
Tue
Set Day/Time
M4953B
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
PM
Tue
Set Day/Time
M4954A
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
Auto
System
Fan
Mon
Room
AM
Occupied 1
Heat
Run
Program