T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
21
63-4355—4
Conventional System
The T7200 and T7300D,F Thermostats with Q7300A,G,H 
Subbases are designed for conventional heat/cool 
applications.
Heat Pump Operation
The T7200E and T7300E,F Thermostats with Q7300C,D,H 
Subbases are designed for heat pump applications. Additional 
information is required when configured for heat pump 
applications.
O AND B TERMINALS FOR HEATING OR COOLING CHANGEOVER
The Q7300C controls heat pump changeover. The Q7300D,H 
is only used in a heat pump application when the heat pump 
controls the reversing valve changeover. See Table 12 for the 
operation of the O and B terminals on the Q7300C, H2003.
O AND B TERMINALS ON A CONVENTIONAL SUBBASE
Conventional subbase O and B terminals can be used to drive 
dampers and valves. The O terminal is energized on a call for 
cool and the B terminal is energized on a call for heat.
Table 12. Operation of Q7300 O and B terminals.
a
When the system is calling for heat or is de-energized, but 
the last function was heat.
b
When the system is calling for cool or is de-energized, but 
the last function was cool.
c
When the last function was heating, the operation is the 
same as Auto (Heat). If the last function was cooling, the 
operation is the same as Auto (Cool).
FAN OPERATION
When the fan is set to On, the fan is energized continuously in 
the Occupied period. The Auto setting energizes the fan with 
the heating or cooling system. If the subbase is Q7300D, the 
fan cycles with Y1 and W1 during Unoccupied period.
EMERGENCY HEAT (SELECT T7300 THERMOSTATS ONLY)
With the system set for Em Heat, auxiliary heat serves as 
stage one; compressor stages are locked off. The fan cycles 
with the auxiliary heat.
COMMUNICATING SUBBASE
Select T7300F Thermostats with the Q7300H Communicating 
Subbase are designed for conventional or heat pump 
applications in a LonWorks® network. The Q7300H Subbase 
allows remote access and the sharing of clock, schedule, 
setpoints, bypass and other system parameters in a 
L
ON
W
ORKS
® network. See Fig. 33 for a T7300F/Q7300H 
wiring layout in a L
ON
W
ORKS
® network.
GENERAL OPERATION INFORMATION
Cycle Rates
The thermostat control algorithm maintains the temperature 
by cycling stages of heating or cooling to meet setpoint.
Subbase Auxiliary Relay
The Q7300 Auxiliary Relay output acts as a time-of-day switch 
to be used with an economizer minimum position control. The 
normally open (A1) auxiliary relay contacts are closed during 
the Occupied period and open during the Unoccupied period. 
The normally closed (A3) auxiliary relay contacts are open 
during the Occupied period and closed during the Unoccupied 
period. The contacts are in the normal state during recovery.
Interfacing with Electromechanical 
Economizers (Subbases with Auxiliary Relay)
Mechanical cooling is often used when outside temperatures 
are in the 50°F (10°C) to 60°F (16°C) range and humidity is 
below 50 percent. In central and northern climates, hundreds 
of hours fall into this temperature category. By permitting 80 to 
100 percent outside air into the system, mechanical cooling 
may not be needed at all, particularly during Spring and Fall.
An economizer is used to take advantage of the outside air. 
The typical economizer consists of an outside air damper, 
motor, outdoor air changeover control and a minimum position 
potentiometer. The motor controls the dampers. Suitability of 
the outside air for cooling is determined by the outdoor air 
changeover control. The potentiometer is used for adjusting 
the minimum position of the economizer dampers, which 
provide a minimum amount of fresh air for ventilation.
The economizer reduces compressor run time, thereby saving 
energy and extending the compressor life. The drawback to 
using the economizer is that during the Unoccupied period, if 
there is no call for cool or outdoor air is not suitable for free 
cooling, the economizer is controlled to minimum position. 
This position allows some percentage of outdoor air to enter 
the building, regardless of air suitability. The situation can 
cause the heating or cooling to run more often than if suitable 
outdoor air is permitted to enter the building.
The thermostat can take advantage of an economizer by 
connecting the subbase auxiliary relay contacts (A1 and A2) 
to control the economizer minimum position potentiometer. 
The contacts close during the Occupied period, allowing the 
economizer to operate normally. The contacts open during the 
Unoccupied period, disabling the minimum position feature of 
the economizer. The open contacts cause the economizer to 
drive dampers fully closed instead of staying at minimum open 
position. This reduces the possibility of unsuitable outdoor air 
from entering the building, which lowers the internal load on 
the HVAC system and saves additional energy.
Other Uses for the Auxiliary Relay
Examples of other uses of the auxiliary relay are hot water 
heaters, lighting or baseboard heat. The additional loads are 
connected to the auxiliary relay contacts on the subbase. The 
contacts are rated for 1.6A at 30 Vac, but can be adapted to 
higher current applications with the use of an external relay 
and transformer. See Fig. 19.
System Selection
O Terminal
B Terminal
Heat
Open
Closed
Cool
Closed
Open
Auto (Heat)
a
Open
Closed
Auto (Cool)
b
Closed
Open
Emergency Heat
Open
Closed
Off
c
c