Locate and Mount C7189U Remote Indoor 
Temperature Sensor (Optional)
1. Choose a location (see Fig. 27) for mounting the sensor 
on an inside wall about 5 ft (1.5m) above the floor. A   
vertically-mounted standard 2 x 4 in. (51 x 102 mm) 
junction box can also be used.
2. Be sure wire distance between C7189 and thermostat is 
less than 200 feet.
3. Make sure there is good air circulation at average 
temperature at the chosen location. Avoid the following 
locations because they can introduce errors in sensor 
measurements. See Fig. 27.
a. Hot areas caused by:
(a) Concealed pipes or ducts.
(b) Drafts from fireplaces or other heat sources.
(c) Convection or radiant heat from the sun or 
electrical equipment.
b. Cold areas caused by:
(a) Concealed pipes or ducts.
(b) Drafts from windows and doors.
(c) Unheated areas on the other side of the wall 
location.
c. Dead air areas:
(a) Behind doors, furniture and curtains.
(b) In corners and alcoves.
4. Mark the area on the wall selected for mounting the 
C7189 Sensor or junction box.
5. Run wire cable to a hole at the selected wall location. 
Pull approximately three inches of wire through the 
opening. Color-coded, 18-gauge thermostat wire is 
recommended.
Fig. 27. Typical location for C7189 Indoor Sensor.
Wire C7189 Indoor Sensor
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation. 
Keep wiring at least one foot away from large inductive 
loads such as motors, line starters, lighting ballasts 
and large power distribution panels. 
IMPORTANT
Erratic temperature readings from a sensor can 
occur as a result of any of the wiring practices 
described below. Avoid these practices to assure 
correct operation. 
— Be sure wires have a cable separate from the 
thermostat cable.
— Do not route temperature sensor wiring with building 
power wiring, next to control contactors or near light 
dimming circuits, electric motors or welding 
equipment.
— Avoid poor wiring connections.
— Avoid intermittent or missing building earth ground.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable codes, ordinances and 
regulations.
1. Wire C7189 Indoor Sensor to S1and S2 terminals on 
the thermostat. For an example of general wiring of 
C7189, see Fig. 28 to wire one sensor and 29 to wire 
multiple sensors. 
2. Push excess wire back into the hole. Plug the hole 
using nonhardening caulk, putty or insulation to prevent 
drafts from affecting performance.
3. Remove C7189 cover.
4. Mount C7189 to the wall or junction box using the 
screws and anchors provided.
5. Level the C7189 for appearance only. Device functions 
correctly even when not level.
6. Install C7189 cover.
5 FEET
(1.5 METERS)
YES
NO
NO
NO
M4476