Control Dehumidification Setting (Select Models)
Select models read the inside humidity level and allow for a 
dehumidification setting:
1. Press the More key until the inside humidity percent and 
dehumidification setpoint are shown. 
2. Use Up and Down arrow keys, located to the right of the 
dehumidifier setpoint, to set desired humidity level  for 
dehumidification in the summer. 
3. Press Done key.
Dehumidification Droop Control
The dehumidification control attempts to control to the user's 
humidity setpoint by turning on the air conditioner. In 
extremely high humidity conditions, the thermostat keeps the 
air conditioner running (energizing Y and G) for up to 3°F 
below the temperature setpoint. It does this while trying to 
achieve the desired humidity setpoint and balancing that with 
the temperature setpoint. The thermostat controls up to 3° F 
below the temperature setting until either the humidity is 
satisfied or conditions change.
Special Heat Pump Operation
Heat Pump LED Indication (Requires 24 Vac 
Common Connection)
A red LED indication is located in the upper right corner of the 
thermostat.  It is only visible when lighted.  
When the L terminal is wired to an equipment monitor, the 
LED signals when a check or fail signal is sent to the 
thermostat from the system.  This is operational in the Heat, 
Off, Cool or Auto positions. See Fig. 32.
Fig. 32. L terminal switch to R (power) side of system 
transformer.
Heat Pump Emergency Heat LED Indication 
(Requires 24 Vac Common Connection)
The thermostat uses a red LED indicator that lights when the 
thermostat is in the Emergency Heat mode.  The LED is 
located in the upper right corner of the thermostat.  It is visible 
only when on.  When the thermostat is in the Em. Heat system 
mode, the L terminal is continuously energized and the LED is 
on.
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor Temperature 
Sensor
In this operation, there is no external fossil fuel kit (dual fuel 
kit) installed; the thermostat controls this function.
1. Choose correct heat pump application in Installer Setup 
Number 0170.
2. Choose Fossil Fuel Option as the backup heat source 
in Installer Setup Number 0200.
3. Choose No External Fossil Fuel Kit Option is control-
ling back up heat in Installer Setup Number 0210.
4. Choose Outdoor Temperature Sensor for Heat Pump 
Temperature Lockouts Option in Installer Setup Num-
ber 0340.
5. Choose appropriate Balance Point Temperature in 
Installer Setup Number 0350.
OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR 
TEMPERATURE)
When the outdoor temperature is above the selected Balance 
Point Temperature (ISU 0350), only the compressor operates 
and the fan (G terminal) energizes when the thermostat calls 
for heat. See Fig. 33.
Fig. 33. Dual Fuel Heat Pump Operation in Heat mode with 
Balance Point Set.
OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR 
TEMPERATURE)
When the outdoor temperature is below the selected Balance 
Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary 
heat) operates and the fan (G terminal) does not energize 
when the thermostat calls for heat.
DONE
CANCEL
DEHUMIDIFIER
Inside
 
Humidity
M19967
M19907
EQUIPMENT
MONITOR
L
TO R
TO C
C
30
M22441
BALANCE
POINT
COMPRESSOR ONLY
FOSSIL FUEL ONLY
OUTDOOR TEMPERATURE