TROUBLESHOOTING (TABLE 14)
Table 14. Troubleshooting.
Symptom
Possible Cause
Action
Display does not come on.
Thermostat is not being powered.
Check for 24 Vac between C and Rc.
Check that AAA batteries are installed 
correctly and are good. 
Temperature settings do not 
change.
The upper or lower temperature limits 
were reached.
Check temperature setpoints.
Check Installer Setup Numbers 0600 and 
0610; modify as needed.
The keypad is fully locked.
Check Installer Setup Number 0670 to 
change keypad locked options.
Heating or cooling does not 
come on.
Thermostat minimum off-time is 
activated.
Wait up to five minutes for the system to 
respond.
System selection is not set to Heat or 
Cool.
Set system Selection to correct position.
System type Selection is incorrect.
Check Installer Setup Number 0170 and 
make sure correct System type is chosen.
Thermostat is calling for Heat 
(Heat on) or Cool (Cool on) but 
no heating or cooling is 
running.
Heating or cooling equipment is not 
operating.
Check wiring.
Check Installer Setup Number 0170 and 
make sure correct system type is chosen.
Verify operation of equipment in System Test 
mode.
Heat does not turn on (Heat 
On is solid in the display).
Heating equipment failure.
Check for 24 Vac at the equipment on the 
secondary side of the transformer between 
power and common. If voltage is not present, 
check the heating equipment to find the cause 
of the problem.
Check for 24 Vac between the heat terminal 
(W) and transformer common. If 24 Vac is 
present, the thermostat is functional. Check 
the heating equipment to find the cause of the 
problem.
Loose or broken wire connection 
between thermostat and heating 
equipment.
Check for 24 Vac between the heat terminal 
(W) and transformer common. If voltage is not 
present, check wire connection (loose or 
broken) between the thermostat and the 
heating equipment.
Cooling does not turn on (Cool 
On is solid in the display).
Cooling equipment failure.
Check for 24 Vac at the equipment on the 
secondary side of the transformer between 
power and common. If voltage is not present, 
check the cooling equipment to find the cause 
of the problem.
Check for 24 Vac between the cool terminal 
(Y) and transformer common. If 24 Vac is 
present, the thermostat is functional. Check 
the cooling equipment to find the cause of the 
problem. 
Loose or broken wire connection 
between thermostat and cooling 
equipment.
Check for 24 Vac between the cool terminal 
(Y) and transformer common. If voltage is not 
present, check the wire connection (loose or 
broken) between the thermostat and the 
cooling equipment.
Fan does not turn on in a call 
for heat (electric furnace).
Fan Control in Heating is set to Gas or 
Oil Furnace (Setting 0180).
Set Fan Control in Heating to Electric Furnace 
(Setting 0180).