Maintenance Object Repair Procedures 
9-363
CABINET (Cabinet Sensors) 
9
Replacing the Fan Power Filter
The fan power filter (ED-1E554-30) is a metal box located behind the fans on the 
right-hand cable trough as you face the rear of the cabinet. It is not present with 
nonvariable-speed fan assemblies.
!
CAUTION:
The fan power filter can be replaced without powering down the cabinet. To 
avoid damage, you must use the following steps in the order shown. Note 
that the J2F/P2F connectors on the power filter must not be connected 
whenever connecting or disconnecting the J2/P2 connectors on the fan 
assembly.
1. Access the power filter through the rear cabinet doors.
2.
Connect the grounding wrist strap to yourself and the cabinet. The fan 
alarm circuit can be damaged by ESD.
!
CAUTION:
Failure to disconnect the J2F connector on the filter before the J2 
connector on the fan assembly can damage the fan alarm circuits.
3. Disconnect cabinet local cable connector J2F from the P2F connector on 
top of the power filter.
4. Disconnect cable connector J2 from the P2 connector on the fan 
assembly.
5. Loosen the power filter mounting screws using a 5/16” nut driver and 
remove the filter.
!
CAUTION:
Failure to connect the J2 connector on the fan assembly can 
damage the fan alarm circuits.
6. Connect the J2 cable connector of the replacement power filter to the P2 
connector on the fan assembly.
7. Mount the new power filter on the screws and tighten.
8. Connect cabinet local cable connector J2F to the P2F connector on the 
top of the power filter.
9. The fans should start rotating after a 4 second delay.