Lucent Technologies Release 7 Manual Do Utilizador

Página de 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-697
DTMR-PT (Dual Tone Multi-Frequency Receiver Port) 
9
Tone Detector Audit/Update Test (#43)
The DTMR port is refreshed with all time slot information and sanity audit is 
performed on the DTMR port.
2000
ABORT
Response to the test was not received within the allowable time period.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2100
ABORT
Could not allocate the necessary system resources to run this test
1. Retry the command at one-minute intervals a maximum of five times.
2006
ABORT
DTMF detection failed. Make sure that the companding mode administered for 
the system matches that of the Tone Detector: mu-law for TN748, A-law for 
TN420.
1-3
FAIL
DTMF digits were not correctly detected.
1. Run the Short Test Sequence: test port UUCSSpp sh r 1.
2. If the problem persists, the system is still operating properly but system 
capacity will be reduced. In order to restore the system performance to 
normal, replace the Tone Detector circuit pack containing the defective 
DTMR port.
PASS
The DTMR port is able to detect all the touch-tone digits.
Table 9-271.
TEST #43 Tone Detector Audit/Update Test 
Error 
Code
Test 
Result
Description/ Recommendation
None
ABORT
The system was not able to allocate all the resources needed for this test.
1. Wait 1 minute and try again.
2000
ABORT
Response to the test request was not received within the allowable time 
period.
2100
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
Table 9-270.
TEST #42 Tone Detection Verification Test  — Continued
Error 
Code
Test 
Result
Description/ Recommendation
Continued on next page