Lucent Technologies Release 6 Manual Do Utilizador

Página de 453
DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Wire Telephones and Other Equipment 
Page 5-34
Off-Premises or Out-of-Building Stations 
5
Digital Out-of-Building Voice Terminals
Protection is required at both building entrances for digital out-of-building voice 
terminals. There are 2 different types of protectors that can be used to protect 
digital voice terminals and digital line circuit packs in an out-of-building 
environment. The 2 enhanced protectors to use are the 4C3S-75 and the ITW 
Linx. These units provide primary and sneak current protection. For sneak 
current protection, the 4C3S-75 is equipped with a heat coil and the ITW Linx is 
equipped with replaceable fuses.
The 4C3S-75 may only be used with Vintage 14 or newer TN754 circuit packs. 
The 4C3S-75 can be used on all vintages of the TN754B circuit packs. The ITW 
Linx may be used on all vintages of the TN754 and TN754B circuit packs. 
Table 
5-12
 lists the approved protectors.
Protector Ordering Information
Description
Comcode
3B1A (Carbon Block)
102381779
3B1E-W (Wide Gap Gas Tube)
104410147
3C1S (Solid State)
105514756
4B1C (Carbon Block with Heat Coil)
102904893
4B1E-W (Wide Gap Gas Tube w/Heat Coil) 
104401856
4C1S (Solid State with Heat Coil)
104386545
SCP-110 Sneak Current Protector
406948976
220029 Fuse (sneak current protector)
407216316
Table 5-12.
Digital Voice Circuit Protectors
Circuit Pack
Enhanced Primary Protector 
(With Sneak Current Protection)
TN754 V13 or earlier
ITW Linx Only
TN754 V14 or later
4C3S-75 or ITW Linx
TN754B all vintages
4C3S-75 or ITW Linx
TN2181 all vintages
4C3S-75 or ITW Linx
TN2224 all vintages
4C3S-75 or ITW Linx