May 1998
Install and Connect Cabinets 
Page 1-10
Connect AC Power and Ground 
1
6. At the AC load center, connect a 10 AWG (#25) (6 mm
2
) wire to the 
single-point ground block. This ground wire will later be tie-wrapped to the 
trunk cables and connected to the Coupled Bonding Conductor (CBC) 
ground block at the MDF.
AC Load Center is More Than 50 Feet (15.2 m) 
from Cabinet
1. Mount the single-point ground block to any surface between the MCC 
cabinets and the AC load center single-point ground. The single-point 
ground block must be mounted to a non-metallic surface.
2. At the bottom rear of the PPN cabinet, connect a 6 AWG (#40) (16 mm
2
CABINET GROUND wire to the cabinet ground block. See 
3. Route the wire to the single-point ground block and connect.
4. At the first EPN cabinet (if provided), connect a 6 AWG (#40) (16 mm
2
CABINET GROUND wire to the cabinet ground terminal block.
5. Route the CABINET GROUND wire to the single-point ground block and 
connect.
NOTE:
If the EPN cabinet is located remote from the PPN cabinet (in a 
separate room or building), route the EPN CABINET GROUND wire 
to an approved ground.
6. Repeat connecting each EPN cabinet to the single-point ground block.
7. Connect a 6 AWG (#40) (16 mm
2
) ground wire to an unused terminal on 
the single-point ground block.
8. Route the ground wire to the AC load center ground and connect.