Lucent Technologies Release 6 Manual Do Utilizador

Página de 453
DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Connect Cabinets 
Page 1-16
Connect DC Power and Ground 
1
Connect DC Power and Ground
Power Distribution Unit (J58890CH-1 Only)
Rectifier Modules and Battery Interface Unit 
Each rectifier module operates as an integral part of a complete power system 
with battery backup. The modules operate in a redundant, high reliability mode to 
provide -48 VDC at 850 Watts to a common power bus.
The Battery Interface Unit (BIU) controls the rectifier modules, manages the 
batteries, and reports the status of system power. The BIU provides the Remote 
Power Off (RPO) option and battery alarm interfaces for internal and external 
alarms.
Figure 1-6.
Rectifier Module Installation
Figure Notes
1. Install Battery Interface Unit into Slot 1
2. Install Rectifier Modules into Slots 2-5
3. Rectifier Module 3 (in Slot 4)
4. Test Points
5. Main Circuit Breakers