DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install Telecommunications Cabling 
Page 2-28
Station Wiring Design 
2
Station Wiring Design
The following hardware and cabling is used:
Information outlets (modular wall jacks)
Station Cables
A brief description of each of the above listed items follows. Ordering information 
is not provided for station cables and information outlets.
Information Outlets
Information outlets are 8-pin modular wall jacks. Most of the outlets are wired with 
push-on connections. Information outlets are also available that connect to a 
double modular plug-ended 4-pair station cable routed from the MDF, a 
site/satellite location, or an adapter.
Station Cables
For clarity, a station cable is either a 25-pair cable, multiple 25-pair cable, or 
4-pair D-inside wire (DIW) run from the equipment room, site/satellite location, or 
adapter to the information outlets. The following station cables are available. See 
25-pair station cable
 
— 
Use between the equipment room and site/ satellite 
locations or adapters. Use an A25D cable (male to male) between the equipment 
room and satellite closet. Use a B25A cable between the equipment room and 
site closet or adapter.
Multiple 25-pair station cable
 
— 
Use between the equipment room and 
site/satellite locations or adapters. This cable consists of individually sheathed 
25-pair cables with a factory-installed 25-pair connector on each end. Use a 
male to female cable to connect between the equipment room and site location 
or adapter. Use a male to male cable to connect between the equipment room 
and satellite location. Staggered-finger cables are recommended for all multiple 
25-pair station cables and are available in both double-ended and single-ended 
types.