22 
SECTION 11: USER INSTRUCTIONS
11.1 User Instructions
The UHA[S] Series heaters are fully automatic and 
operate from the external controls fitted on site. 
11.2 Heater Operation
When the heater has been switched on by the 
thermostat installed on site, the main burner will 
automatically turn on.
The burner control box will control the safe ignition 
of the flame.
All heaters require a constant gas and electricity 
supply which must not be interrupted during the 
normal operation of this heater.
11.3 Lighting Instructions 
11.3.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to 
the heater are on. Check that the on site 
controls are "ON".
NOTE: The thermostat setting must be above the 
ambient temperature for the heater to operate.
2. The automatic firing sequence will begin as 
described on Page 20, Figure 10. The heater 
will now operate automatically under the control 
of the on site controls.
11.3.2 To Turn the Heater Off 
Set the thermostat to the "OFF" position.
The burner will turn off immediately.
The fan will continue to run for 90 seconds. 
To restart, turn the thermostat above room 
temperature.
11.4 Simple Troubleshooting
Some possible reasons for the heater not operating 
are:
1. Gas supply not "ON".
2. Electricity supply not "ON".
3. The time and/or temperature controls are not 
"ON".
4. A limit switch may have operated. This may be 
caused by an interruption of the electrical 
supply, failure of the distribution fan or vent or 
heat exchanger blockage.
If a temperature limit switch persistently trips, there 
is a fault which must be investigated by a contractor 
qualified in the installation and service of gas-fired 
heating equipment.
11.4.1 Simple Troubleshooting (Burner Fault)
If the burner fails to ignite for any reason, it will retry 
for ignition (4 trials total). After 4 unsuccessful 
ignition trials, the control will put the heater into 
lockout for 1 hour.
Lockout should not occur during normal operation of 
the heater and indicates there is a fault condition 
which must be corrected. There is an LED light on 
the ignition control that flashes codes to assist in 
fault correction. See Figure 12 for LED indication 
codes.
Figure 12: LED Diagnostic Codes
WARNING
Electrical Shock Hazard
Disconnect electrical power before servicing.
Failure to follow these instructions can result in
death or electrical shock.
LED INDICATION FAULT MODE
Slow Flash
Normal Operation - No call for heat.
Fast Flash
Normal Operation - Call for heat.
2 Flashes
Ignition Lockout - No flame detected.
3 Flashes
Airflow Fault - Pressure switch open or closed.
4 Flashes
Temperature Limit or 
Manual Reset Limit Switch Open
5 Flashes
Flame Sense Error - Gas valve not energized.
Steady On
Internal Control Failure