Replacing the Battery
The battery in the ION8800 meter keeps the real time clock running when 
supply power is lost. Replace the battery if the meter has been stored for an 
extended period of time without power (longer than two years). If the meter 
will be without power for an extended length of time, disconnect the battery 
cable so that the battery maintains its 10-year shelf life.
The battery can be changed when the meter is either powered or 
unpowered. 
N
OTE
Replacing the battery on an unpowered meter resets the internal clock and
may affect revenue parameters.
To replace the battery
1.
To prevent electrostatic damage to the unit, make sure you are 
grounded or wear an anti-static wrist strap during this procedure.
2.
Open the front cover of the meter.
3.
Remove the Phillips screw that holds the battery cover in place and 
remove the battery cover.
4.
Remove the battery from the housing and disconnect the battery 
connector from the meter.
5.
Connect the new battery’s wire to the meter. and place the battery in the 
housing. 
6.
Replace the battery cover and the Phillips screw. 
7.
Close the cover of the meter.
Battery Specifications
Type
Lithium LiSOCl
2
Nominal Capacity
1.0 Ah
Rated Voltage
3.6 V
Connector
Gold-plated
Battery Dimensions
Gold-plated 
Connector
Battery
Battery 
Connector
Battery Cover