Hitachi CONVENTION 14 Manual Do Utilizador

Página de 305
General Specifications
The following table applies to all X200 inverters.
Item
General Specifications
Protective housing *1
IP00
Control method
Sinusoidal Pulse Width Modulation (PWM) control
Carrier frequency
2kHz to 12kHz (default setting: 3kHz)
Output frequency range *4
0.5 to 400Hz
Frequency accuracy
Digital command: 0.01% of the maximum frequency
Analog command: 0.4% of the maximum frequency (25
qC r 10qC)
Frequency setting resolution
Digital: 0.1Hz; Analog: max. frequency/1000
Volt./Freq. characteristic
V/f control (constant torque, reduced torque)
Overload capacity
150% rated current for 1 minute
Acceleration/deceleration 
time
0.01 to 3000 seconds, linear and S-curve accel/decel, second
accel/decel setting available
Operator panel
Up and Down keys / Value settings
Potentiometer
Analog setting
Freq.
setting
External signal
*9
0 to 10 VDC (input impedance 10k Ohms), 4 to 20mA (input
impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W)
Operator panel
Run/Stop (Forward/Reverse run change by command)
FWD/
REV run External signal Forward run/stop, Reverse run/stop
Input
signal
Intelligent input
terminal
FW (forward run command), RV (reverse run command), CF1~CF4
(multi-stage speed setting), JG (jog command), DB (external
braking), SET (set second motor), 2CH (2-stage accel./decel.
command), FRS (free run stop command), EXT (external trip), USP
(startup function), SFT (soft lock), AT (analog current input select
signal), RS (reset), PTC (thermistor thermal protection), STA (start),
STP (stop), F/R (forward/reverse), PID (PID disable), PIDC (PID
reset), UP (remote control up function), DWN (remote control down
function), UDC (remote control data clearing), OPE (operator
control), ADD (add frequency enable), F-TM (force terminal mode),
RDY (Run ready), SP-SET (Special set) , EMR (Emergency Stop)
Intelligent output
terminal
RUN (run status signal), FA1,FA2 (frequency arrival signal),
OL (overload advance notice signal), OD (PID error deviation
signal), AL (alarm signal), Dc (analog input disconnect detect),
FBV (PID two-stage control output), NDc (network detection signal),
LOG (Logic output), ODc (comm. watchdog error), LOC (Low load)
Output
signal
Frequency monitor
Analog output; Select output frequency or output current monitor
Alarm output contact
ON for inverter alarm (1c contacts, both normally open or closed
avail.)
Other functions
AVR function, curved accel/decal profile, upper and lower limiters,
16-stage speed profile, fine adjustment of start frequency, carrier
frequency change (2 to 12kHz) *10, frequency jump, gain and bias
setting, process jogging, electronic thermal level adjustment, retry
func., trip history monitor, 2nd setting select, fan ON/OFF selection.
Protective function
Over-current, over-voltage, under-voltage, overload, extreme high
temperature, CPU error, memory error, ground fault detection at
startup, electronic thermal
Temperature
Operating (ambient): -10 to 40
qC(*10), / Storage: -25 to 70qC(*11)
Humidity
20 to 90% humidity (non-condensing)
Vibration *12
5.9m/s
2
 (0.6G), 10 to 55 Hz
Operating
environment
Location
Altitude 1,000m or less, indoors (no corrosive gasses or dust)
Coating color
Blue
Options
Remote operator unit, copy unit, cables for the units, braking unit,
braking resistor, AC reactor, DC reactor, noise filter
1
10
Getting st
arted
1
−10
Getting started