Parallel Compressor Systems Installation & Operations Manual, October 2004  
5
Compressor Spring Vibration Isolators
On units with this option, the compressors are secured rigidly 
to make sure there is no transit damage. Before operating the 
unit, it is necessary to follow these steps:
1. Remove the upper nuts and washers
2. Discard the shipping spacers
3. Install the neoprene spacers (Spacers located in the electrical 
panel or tied to compressor)
4. Replace the upper mounting nuts and washers
5. Allow 1/16 inch space between the mounting nut/washer 
and the neoprene spacer
Parallel Compressor Systems
Location of Equipment - Outdoor
The mounting platform or base should be level and located 
so as to permit free access of supply air.
Units must not be located in the vicinity of steam, hot air 
or fume exhausts.
The unit should be mounted away from  noise sensitive 
spaces such as offices.
The unit must have adequate support to avoid vibration and 
noise transmission into the building. Sound and structural 
consultants should be retained for recommendations.
Ground Mounting
The unit must be set on a flat and level foundation. A single 
piece concrete slab with footings extending below the frost 
line and raised approximately six inches above ground level 
provides a suitable base. Raising the base above ground level 
provides some protection from ground water and wind blown 
matter. The concrete slab should be isolated from the building 
structure. Finally, before tightening mounting bolts, recheck 
the level of the unit.
Roof Mounting 
Rooftop installations require adequate structural beams to 
support the weight of the unit and service personnel. The 
design of the beams/supports must minimize deflection and 
attendant vibration transmission.
Due to the weights involved, a structural analysis by a qualified 
engineer may be required before mounting. Also, for sound 
sensitive applications, unit vibration isolators should be used.
Unit Vibration Isolation
Under  certain  critical  conditions,  it  is  recommended  that 
vibration isolators, of a suitable type, be installed under the 
base. The isolators must be designed for the operating weight 
of the unit. Rubber-in-shear or spring type isolators (by others) 
are available for this purpose.
Figure 3. Spring Mount
absorbing spring mounts (optional equipment) must be placed 
under the base frame of each unit. See Figure 1 for view of 
Spring Isolator. The spring mounts are placed under the unit 
and the unit carefully lowered on to the mounts. Note that no 
other mounting hardware is required and any unevenness in 
the floor or uneven weight distribution may be compensated 
for by turning the spring mount leveling nuts with an open-
end  wrench.  This adjustment should be made after all piping 
is installed and the system is charged with refrigerant.