CHAPTER 12 External Interfaces
12.1
UPS Control Interface
Overview
The UPS control interface is used to perform temporary data saving processing. In this processing, a
reserved interruption for software occurs when the uninterruptible power supply (UPS) is used to
backup a power failure in the commercial AC power supply. In addition to this type of UPS control
interface, there are several other UPS units that use the general-purpose interface such as RS232C.
Connecting interfaces
The configurations and definitions of the signal lines to be connected to the UPS system are shown
below. Do not use pin numbers unspecified below to connect to the UPS system.
Table 12.1
Definitions of UPS Signal Lines
 Signal                        Definitions                     Pin                      Remarks               
 names                                                               Nos.                      
BPS             Signal indicating faulty UPS         6          Enabled with ON.      
                    conditions                                              
BTL            Signal indicating that the UPS       7          Enabled with ON.      
                    battery level has lowered and                           
                    that ineffectual battery char                           
                    ge may result after a certain                           
                    period of time (*1)                                     
UPSON       Signal indicating the UPS is          8                         
                    operating                                               
ACOFF       Signal notifying power failure       9          When power fails: ON  
                    in the commercial AC supply                    When power is normal: 
                    connected to the UPS (*2)                         OFF                   
SG               System ground signal                    5                         
ER (*4)       Signal indicating the main             1                         
                    cabinet is operating (*3)                               
ON indicates contacts are closed.
OFF indicates contacts are open.
*1
The normal power supply should be maintained by the UPS battery for at least 10 to
60 seconds after the connecting interface signal is turned on.
*2
For momentary power supply interruption of the commercial AC power not
exceeding two seconds, the normal battery power supply without activating ACOFF*
is recommended.
*3
This connecting interface signal identifies the status of the main cabinet to prevent
supplying battery power in case the signal is in the OFF (LOW) state (the main
cabinet is stopped), even though a power failure is detected by the UPS.
*4
ER signal may be left unused.