Chapter 8: Managing External Devices 
 
 
167
 
 
5.  In the Wait Time (in seconds) before Resuming Pinging field, type 60 
to make the EMX stops pinging the target PDU for 60 seconds (1 
minute) after the PDU inaccessibility is declared. After 60 seconds, 
the EMX will re-ping the target PDU. 
 
Step 2: Create an event rule to send SNMP notifications for this 
PDU 
1.  Choose Device Settings > Event Rules. The Event Rule Settings 
dialog appears. 
2.  Click New. 
3.  In the "Rule name" field, type "Send SNMP notifications for PDU 
(192.168.84.95) inaccessibility." 
4.  Select the Enabled checkbox to enable this new rule. 
5.  In the Event field, choose Server Monitoring > 192.168.84.95 > 
Unreachable. 
6.  In the "Trigger condition" field, select the Unreachable radio button. 
This makes the EMX react only when the target PDU becomes 
inaccessible. 
7.  Select the System SNMP Notification Action from the "Available 
actions" list box, and click 
 to add it to the "Selected actions" list 
box. 
Note: If you have not configured the System SNMP Notification Action to 
specify the SNMP destination(s), see 
Configuring SNMP Notifications
 
(on page 204). 
 
 
Editing Ping Monitoring Settings 
You can edit the ping monitoring settings for any IT device whenever it 
requires changes. 
 
To modify the ping monitoring settings for an IT device: 
1.  Choose Device Settings > Server Reachability. The Server 
Reachability dialog appears. 
2.  Select the IT device whose settings you want to modify by clicking it. 
3.  Click Edit or double-click the IT device. The Edit Server 'XXX' dialog 
appears, where XXX is the IP address or host name of the IT device. 
4.  Make changes to the information shown. 
5.  Click OK to save the changes.