Chapter 8: Managing External Devices 
 
182
 
 
 
After a sensor is removed from management, the ID number assigned to 
that sensor is released and can be automatically assigned to any newly-
detected sensor. 
 
Threshold Information 
Setting and enabling the thresholds causes the EMX to generate alert 
notifications when it detects that any sensor's state crosses the 
thresholds. 
There are four thresholds for each sensor: Lower Critical, Lower 
Warning, Upper Warning and Upper Critical. 
 
Upper and Lower Warning thresholds indicate the sensor reading 
enters the warning range before the critical threshold. 
 
Upper and Lower Critical thresholds indicate the sensor reading is at 
the critical level. 
To avoid generating a large amount of alert events, the deassertion 
hysteresis for each threshold is enabled. You can change the default 
hysteresis value if necessary. For more information on the deassertion 
hysteresis, see 
What is Deassertion Hysteresis?
 (on page 182). 
Note: After setting the thresholds, remember to configure the event rules. 
See 
Configuring Event Rules
 (see "
" on 
page 131). 
For information on configuring an environmental sensor's threshold, see 
Configuring Environmental Sensors
 (on page 172). For information on 
configuring thresholds for a Schroff LHX heat exchanger, see 
Configuring Temperature and Fan Thresholds
 (see "
" on page 194). 
 
What is Deassertion Hysteresis? 
The hysteresis setting determines when a threshold condition is reset. 
This diagram illustrates how hysteresis values relate to thresholds: 
 
 Hysteresis 
Upper Critical Threshold 
Upper Critical Reset 
 
 
 Hysteresis 
Upper Warning Threshold 
Upper Warning Reset